Commissioning
Setting options via switches
Node address setting
)
Note!
The address must be set via software, when the switches S7 and S8 are in
ON−position.
In this case the switches S1 to S6 are ineffective.
ON
1
2
3
4
Fig. 2
Node address setting
)
Note!
If several controllers are connected to the network, the node addresses must
differ from each other.
The address (decimal number) is calculated by inserting the positions of switches S1 to S6
('0' = OFF and '1' = ON) into the following equation.
Address
= S6 · 2
dec
The equation can also be used to calculate the valency of a switch. The sum of valencies
results in the node address to be set:
Switch
S1
S2
S3
S4
S5
S6
58
5
6
7
8
9
0
1
2
+ S5 · 2
+ S4 · 2
Valency
32
16
8
4
2
1
10
3
4
+ S3 · 2
+ S2 · 2
+ S1 · 2
Switch position
ON
ON
ON
OFF
OFF
OFF
l
ON
OFF
5
Example
Node address
32 + 16+ 8 = 56
EDK82ZAFVC010 DE/EN/FR 2.0