3
Electrical installation
Cable specification
Features of the Thick" cable according to DeviceNet specifications
General features
Configuration
Total shielding
Drain wire
Outer diameter
Roundness
Jacket marking
Spec. DC resistor (braid, tape, drain)
Certifications (U.S. and Canada)
Bend radius
Ambient operating temperature
Storage temperature
Pull tension
Features of the data line
Conductor pair
Insulation diameter
Colours
Pair twist / m
Tape shield over conductor pair
Impedance
Capacitance between conductors
Capacitance between a condcutor and the
conductor connected to the shield
Capacitive unbalance
Spec. DC resistor at 20ºC
Attenuation
Features of the voltage line
Conductor pair
Insulation diameter
Colours
48
Two shielded symmetrical cables with a common axis and drain wire in
the centre
65% coverage
AWG 36 or min. 0.12 mm tinned braid (individually tinned)
Copper 18 min.; min. 19 cores (individually tinned)
10.41 mm (min.) to 12.45 mm (max.)
Radius deviation must be within 15% of 0.5 outer diameter
Vendor name & part no. and additional markings
5.74 Ohms/1000 m (nominal up to 20°C)
NEC (UL), CL2/CL3 (min.)
20 x diameter (installation) / 7 x diameter (fixed)
−20°C to +60°C at 8 Ampere; derate current linearly to zero at 80°C
−40 to +85°C
845.5 N. max.
Copper 18 min.; min. 19 cores (individually tinned)
3.81 mm (nominal)
Light−blue, white
Approx. 10
2000/1000, Al/Mylar, Al side out, w−shorting fold (pull−on applied)
120 Ohms +/− 10% (at 1 MHz)
39.37 pF / m at 1 kHz (nominal)
78.74 pF / m at 1 kHz (nominal)
3937 pF/1000 m at 1 kHz (nominal)
22.64 Ohms/1000 m (max.)
0.43 dB/100 m at 125 kHz (max.)
0.82 dB/100 m at 500 kHz (max.)
1.31 dB/100 m at 1.00MHz (max.)
Copper 15 min.; min. 19 cores (individually tinned)
2.49 mm (nominal)
Red / black
l
EDK82ZAFVC010 DE/EN/FR 2.0