Status Of Terminal Outputs; Test And Maintenance Status - Comelit FG100F Manuel Technique

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Status of terminal outputs

Reporting type
Regular Device
Communication error
Faulty smoke generator
Used-up smoke generator
Generic error

TEST and MAINTENANCE status

This mode is automatically activated, at first power-up, by pressing the RESET button, and
whenever the enclosure is opened. The "TEST and MAINTENANCE" mode is terminated when the
enclosure is closed. A 15-second timing at both the opening and closing of the enclosure avoids
the possibility of sabotage of the device.
When in this mode:
• a single BLUE flash blinks every 3 seconds.
• the smoke emission is disabled.
• if the IN FUM input is activated (alarm condition), the siren emits a CONTINUOUS sound, and
the RED LED blinks rapidly.
• if the IN SIR input is activated (alarm condition), the siren emits a MODULATED sound, and the
RED LED blinks rapidly.
Please enter this mode for checking cabling, connections, and dip-switches setup, without risks
of unwanted smoke emissions.
• Warning! When you want to activate the AND feature (SW6=ON), please perform tests by
first DISABLING this feature, and checking inputs one by one. Then RE-ENABLE the AND
feature. Please remember to push the RESET button after switching one or more dip-
switches, to apply the configuration.
The following time diagram shows the state behaviour of "TEST and SERVICE".
Output Finish Smoke
generator (OUT END)
GND
GND
OPEN
OPEN
GND
Error output
(OUT ERR)
GND
OPEN
OPEN
GND
OPEN
27