Programming siren sound duration
The sound time of the piezoelectric siren can be programmed via the SW4 switch of the Siren Time
according to the following table:
ON
Follow Siren input ON time (max sound time 15 minutes)
SW-4
OFF
60 seconds
AND function for inputs
Using the SW6 switch, you can choose how the smoke generator is activated according to the
following table:
The smoke generator is activated only if the smoke input IN FUM is alarmed
ON
when the siren input is already alarmed.
SW-6
The smoke generator is activated immediately when the smoke input IN FUM
OFF
is alarmed.
Anti-opening and anti-tear Tamper
The anti-opening and anti-tear tamper refer to a single OUT TAMP output. In Normal state (closed
enclosure and anti-tear switch engaged) the output is Normally Closed to a Zero Voltage (GND). In
case of anomaly, the output is an Open Contact.
Tear control can be enabled/disabled using the SW5 switch as per table:
ON
Enabled
SW-5
OFF
Disabled
Meaning of LED
The activity and status of the device are highlighted by a multicolor LED at the bottom of the body
and by the status of the outputs "USED-UP SMOKE GENERATOR" and "ERROR".
According to the following scheme, the system status information is shown every 6 seconds.
25