Installation and operating instructions
sensor for schools (CO2 Monitor ) with traffic light display, incl. power supply unit, self-calibrating, in an el-
Maintenance-free CO
2
egant plastic housing, for determining the CO
urand to a standard signal, which is directly presented visually by five coloured LEDs (traffic light indicator). Available in device
versions CO2 AP for direct wall mounting, CO2 UP for mounting on in-wall flush boxes and CO2 AP-A as a floor-mounted device
with a metal support.
The room sensor is used in classrooms, training rooms and convention centres, offices, hotels, apartments, shops, etc. and is
used for easy and quick evaluation of the indoor climate. This enables energy-saving room ventilation on an as-needed basis,
thereby reducing operating costs and improving well-being. The CO
(non-dispersive infra-red technology).

TECHNICAL DATA

Power supply:
Electrical connection:
Sensor:
Measurement range:
Measuring accuracy:
Temperature dependence:
Pressure dependence:
Long-term stability:
Gas exchange:
Ambient temperature:
Warm-up time:
Response time:
Housing:
Dimensions:
Installation:
Protection class:
IP rating:
Standards:
Equipment:
CO2 Monitor
CO
2
Type
Measuring
ranges CO
CO2 Monitor
C O2 A P
0...3000 ppm
C O2 A P-A
0...3000 ppm
C O2 U P
0...3000 ppm
Note:
This unit must not be used as safety-relevant device!
CO2 Monitor
content of room air (0...3000 ppm). The measuring transducer converts the meas-
2
CO2 UP: 24 V AC ⁄ DC (± 10 %)
CO2 AP, CO2 AP-A: 230 V AC (50 -60 Hz)
power supply unit 230 V ⁄ 50 -60 Hz (included in the scope of delivery)
optical NDIR sensor (non-dispersive infrared technology),
with manual calibration (via zero button) with automatic calibration
0...3000 ppm
typically ± 30 ppm ± 3% of measured value
± 5 ppm ⁄ °C or ± 0.5% of measured value ⁄ °C (whichever is greater)
± 0.13% ⁄ mm Hg
< 2% in 15 years
by diffusion
0...+ 50 °C
approx. 1 hour
< 2 minutes
plastic, material ABS, colour pure white (similar to RAL 9010)
85 x 85 x 27 mm (Baldur 1)
CO2 UP, CO2 AP: wall mounting or on in-wall flush box, Ø 55 mm, base with 4-hole for mounting
on vertically or horizontally installed in-wall flush boxes for cable entry from the back, with pre-
determined breaking point for on-wall cable entry from top ⁄ bottom in case of plain on-wall
installation
CO2 AP-A: mobile CO
III (according to EN 60 730)
IP 30 (according to EN 60 529)
CE-conformity, electromagnetic compatibility
according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU,
low voltage directive 2014 ⁄ 35 ⁄ EU
traffic light indicator (five coloured LEDs, see table)
for displaying the CO
Connector for power supply unit (connecting cable approx. 1.5 m) or
in-wall power supply unit for mounting on in-wall flush boxes (CO2 UP)
Stand holder made from stainless steel (CO2 AP-A)
sensor for schools with traffic light indicator incl. power supply unit
Display
CO
2
2
5 LEDs
5 LEDs
5 LEDs
measurement is performed using an optical NDIR sensor
2
measuring instrument on stand holder (table-top unit)
2
concentration
2
Equipment
Connector for power supply unit
Connector for power supply unit, stand
holder
In-wall power supply unit
7
Item no.
with traffic light
4 010 7
4 010 9
4 010 8