8.0

Technical data

Operating voltage:
Frequency
Control voltage:
Power consumption
(contactors attracted)
Power consumption in quiescent state: < 10 VA
Max. connected load
Range of electrical motor current
limitation
(The limit values specified in the table under section 1.1 of the safety regulations must be observed)
230 V alarm contact
Floating alarm contact
Housing:
Degree of protection:
Pressure range (internal sensor):
Temperature range:
Dimensions:
Fuse:
Voltage supply
for 4 - 20 mA probe:
Subject to technical changes!
9.0

Standards:

Relevant EC Directives:
Applied harmonised standards
In particular:
MultiControl Duo
3 ~ 400V (L1, L2, L3, N, PE)
50/60 Hz
230 V/AC, 50 Hz
< 20 VA
P
< 5.5 kW
2
0.3 - 14 A
1 A
3 A
polycarbonate
IP 54
0 - 2 mWs (optional: 0 - 5 mWs)
-20°C to +60°C
320 x 300 x 120 mm (W x H x D)
5 x 20 1AT (alarm output)
approx. 24 V/DC
EC Low Voltage Directive
2006/95/EC
EC Electromagnetic Compatibility Directive
2004/108/EC
EN 61000 - 6 - 2: 2005
EN 61000 - 6 - 3:2007
EN 61010 - 1:2001 + Amendment 1:2002
+ Amendment 2:2004