Motion Detector Walk Test

IMPORTANT: Before commencing walk test ensure the LED indicator behind the
detector lens is not flashing continuously. If it is wait until the detector has completed
its warm-up cycle and the flashing stops.
Configure the detector for walk testing according to the selected Day or Night operat-
ing mode as follows:
1) Set the TIME control fully counter-clockwise to its minimum setting.
2) If the detector is set to DAY operation (for use with a chime), adjust the DUSK
control fully counter-clockwise to its minimum setting. If the detector is set to
NIGHT operation (for use with lighting) adjust the DUSK control fully clockwise to
its maximum setting.
69-2157EFS_C.indd 9
DUSK CONTROL
DUSK CONTROL
SETTING FOR
SETTING FOR
DAY OPERATION
NIGHT OPERATION
Fig. 5
9
TIME
CONTROL
M27297
RCA902A
69-2157EFS—05
9/22/2008 11:54:00 AM