External Input And External Output (Optional Parts) - Fujitsu Airstage ASYE07GACH Manuel D'installation

Masquer les pouces Voir aussi pour Airstage ASYE07GACH:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 34
(3) Connect the cable of wired remote controller unit to the PCB of Control unit, and set
the DIP switch (SW1). Fasten the remote controller cable to the EV kit cable with the
cable tie as shown below.
When switching the DIP switch (SW1), be sure to turn off the power supply to the
indoor unit. Otherwise, the PC board of the indoor unit may be damaged.
Set the DIP switch (SW1)
2WIRE (Factory setting)
DIP switch
(SW1)
SW1
Connector
(CNC01)
Connecting cable
(Accessories)
Wired remote
controller cable
To EV kit
6.6. External input and external output
(Optional parts)
Controller PCB
DIP switch
(SET 2)
OFF
ON
(CNA03)
Apply voltage terminal
(1) External input
• Indoor unit can be Operation/Stop or Emergency stop or Forced stop by using indoor
unit PCB CNA01 or CNA02.
• "Start/Stop" mode or "Emergency stop" mode or "Forced stop" mode can be selected
with function setting of indoor unit.
• Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
Input select
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
En-11
9377773098-01_IM.indb 11
9377773098-01_IM.indb 11
CAUTION
For 2-wire type
For 3-wire type
3WIRE
10 mm
or less
Cable tie
(Accessories)
Dry contact
terminal
(CNA04)
(CNA02)
Output terminal
(CNB01)
(CNA01)
● Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
DC power supply
12 to 24V
Load
resistance
*a
Load
resistance
*a
Load
resistance
*a
connected unit
*1 Make the power supply DC12 to 24V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
When connected to Apply voltage terminals of multiple indoor units with a connected unit,
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below
example.
DC power supply
12 to 24V
Load
resistance
Load
resistance
connected unit
● Dry contact terminal ([CNA02], [CNA04])
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal ([CNA02], [CNA04]).
*c
*c
Ch 1
Ch 2
*c
Ch 3
connected unit
*c Select very low current use contacts (usable at DC12V, DC1mA or less).
*d The wiring is different from Apply voltage terminals. Be suffi ciently careful when wiring.
When connected to Dry contact terminals of multiple indoor units with a connected unit,
insulate each indoor unit with relay, etc. as shown on below example.
*1
P.C.B
CNA01
*b
CNA03
P.C.B
CNA01
P.C.B
CNA01
P.C.B
CNA01
P.C.B
CNA02
GND
*d
CNA04
7/12/2012 3:05:26 PM
7/12/2012 3:05:26 PM

Publicité

Table des Matières
loading

Table des Matières