Application area
The heater fans type CAT are intended
for heating buildings. The compact and
robust design makes the fans ideal for use
in different areas, e.g. warehouses, garages,
workshops, shops, etc. The heater fans are
approved according to SEMKO, NEMKO,
DEMKO and FIMKO. Enclosure class: Splash-
proof design.
Electrical connection
The heater fans are fitted with a terminal
block for connection to the mains supply
and terminal blocks for connections to an
external isolator, thermostat and timer.
There are two knockouts at the rear for the
external connections that should be fitted
with appropriate grommets to ensure the
enclosure's classification.
The heaters can be connected for either
230V3~ and 400V3N~. The 3 kW model can
be connected for single phase. Note! Other
models cannot be connected for single phase.
Installation
The installation should be permanent
and carried out by a qualified technician
according to applicable directives. The
installation should be preceded by a fully
isolating switch with at least a 3 mm gap and
preferably fitted with a status lamp. Ensure
that the mains voltage and the information on
the type plate correspond. The wiring diagram
can be found in the inside of the cover.
NOTE! The heater must be dead when
carrying out all work on it.
6
Assembly and operating instructions
Assembly
• Note that the minimum distances as sat out
in the figure on page 2 must be maintained.
• The unit must be installed with the
connection area to the left, as seen from the
front.
• Mark out and drill the holes for the screws
as set out in the diagram on page 2.
• Screw in the screws for the keyholes so that
approximately 10 mm remains.
• Hang-up the unit and tighten the screws.
• Screw in the last screw.
Function
Position of the output selector, see
Technical data.
°C
Toggle switch in position °C means
the thermostat only controls the output,
the fan runs continuously.
°C
In position °C
a special thermostat, which only switches
on the fan when the heat is on.
°C
It is possible that the temperature limiter
may have tripped during transport, if the unit
does not function the first time it's switched
on. Rectify as set out in the description under
"Overheating". (Fig. 1)
Overheating
If the unit overheats the integrated
temperature limiter will trip. Reset the
temperature limiter after the unit has cooled
and the fault rectified. (Fig. 1)
NOTE! All work inside the unit's connection
area should be carried out by an authorized
technical and the unit must be dead.
The temperature limiter is reset by removing
the cover and pressing the button on the
temperature limiter. (Fig. 1)
CAT
the fan is controlled by