Vaillant geoTHERM VRC 700 Notice D'installation page 7

Masquer les pouces Voir aussi pour geoTHERM VRC 700:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 27
Work
53
Additional module
54
Status
55
Current flow temp.
56
HEATING 1
57
Type of circuit
58
Status
59
Target flow temp.
60
Max limit outs.temp.
61
Heating curve
62
Minimum temperature
63
Maximum temperature
64
Auto Off mode
65
Room temp. mod.
66
Cooling possible
67
Min. cool. fl. tgt temp.
68
End OT cooling
69
Pump status
70
Dew point monitoring
71
ZONE1
72
Zone activated
73
Day temperature
74
Set-back temp.
75
Room temperature
76
Zone assignment
77
Zone valve status
78
Domestic hot water
79
Cylinder active
80
Target flow temp.
81
Domestic hot water
82
Domestic hot water
83
Cyl. charging pump
841
Circulation pump
85
Anti-legionella day
86
Anti-legionella time
87
Cyl. boost hysteresis
88
Cylinder boost offset
89
Max. cyl. charg. time
90
DHW req. anti-cy time
91
Ch. pump overrun time
92
Parallel cyl. charging
0020251822_01 System installation instructions
Commissioning checklist 3
Comments/settings
Current value display (standby, heating, cooling, do-
mestic hot water)
Current value display
Heating
Current value display (off, heating mode, cooling, do-
mestic hot water)
Current value display
21 °C, change in consultation with the customer, if re-
quired
0.4 to 0.6 for underfloor heating
15 °C
45 °C for underfloor heating
Set-back
None if the control is installed in the heat pump
Temp. mod. if the control is installed in the living room
Yes for underfloor heating
No; you should not use passive cooling for compact col-
lectors and flat collectors
18 °C
15 °C
Current value display: off / On
Yes
Current value display: No / Yes
20 °C
15 °C
Current value display
VRC 700
Condition: VRC 700 installed in the living room, room
temperature modulation activated
Current value display (closed/open)
Condition: Domestic hot water cylinder in the system
Current value display
50 °C
Inform the end user about the anti-legionella function
Current value display
Current value display (off/on)
Current value display (off/on)
Selection: Off, Mo, Tu, We, Th, Fr, Sa, Su, Mo-Su
Factory setting: Off
04:00
Depending on the customer
15 K
10 K
Off: KfW efficient house 40
60 min.: > KfW efficient house 40
0 min.: KfW efficient house 40
60 min.: > KfW efficient house 40
5 minutes
off
5

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Vws 36/4.1Vwz meh 610020235577

Table des Matières