6.
TECHNICAL DATA
6.1.
Operating conditions
WARNING!
Burns, chemical burns through leaking medium.
• Prior to the use of aggressive media, the resistance of the
media-wetted parts must be checked.
You can access the Bürkert Chemical Resistance Chart on the
Internet at
www.buerkert.de
Chemical Resistance Chart. If you are unsure, please contact your
Bürkert Sales Center.
NOTE!
Malfunction!
• Do not use Type 7615 outdoors without the appropriate hous-
ing and avoid heat sources that may cause the permissible
temperature range to be exceeded.
Permitted temperatures
Ambient temperature: +10 to +55°C
Medium temperature: +15 to +60°C (FFKM seals)
+ 5 to +60°C (EPDM seals)
Media:
Neutral and aggressive liquid media. Check suitability
according to the Chemical Resistance Chart.
Protection class: IP40
8
Documentation
Brochures
english
Type 7615
Technical data
6.2.
General technical data
Observe the technical specifications as detailed on the type
plate!
Max. manometric pressure:
Dosing quantity:
Connections:
6.2.1.
Rating plate
Example:
Type
7615 CC
PK
24V
DC
11W
DOSING UNIT
S/N 1050
W16LP
00202784
Fig. 1:
Rating plate description
approx. 1 bar (overpressure towards
the atmospheric pressure)
5 µl/stroke
4-pole Molex connector
(Molex no. 50-57-9404)
Voltage / type of current
Seal material
Housing material
Power
Device designation
Serial number
Date of manufacture
(encoded)
Identification number of
the device