Rev16 28-04-2021
Figure 1: Connection diagram of the BP-65
Figure 2: Connection diagram of the BP-100 and BP-220
Figure 3: Connectors and pin numbering
Figure 4: System with Li-ion battery
Note: The BP will disengage when its control input becomes free floating. If the battery voltage recovers after disconnecting (which will happen
when no other loads are connected to the battery), the output of the Ve.Bus BMS will become high and the BP will re-engage after 30 seconds.
After 3 attempts to re-engage, the BP will remain disengaged until battery voltage has increased to more than 13V (resp. 26V) during at least 30
seconds (which is a sign that the battery is being recharged). The under voltage thresholds and alarm output of the BP are inactive in this mode.
(remote switch can also be connected between pin 2.1 and battery plus)
(protected against short circuit with internal 10kΩ series resistor)