SECTION 9: Troubleshooting Guide. Ener-Radiant XL
START
Turn on thermostat
Does blower turn
No
on?
Yes
Check LED indicator on SmartValve for
indication of fault. Refer to SmartValve testing
on page 20 to determine problem.
Does the igniter
warm up and glow
No
red?
Yes
No
After ignitor warm-
up period, does the
valve click?
The SmartValve checks the status of the blower proving switch contacts must see a change in the
contact with every firing cycle. Placing a jumper at the switch out of sequence will result in a fault with
Yes
Does the burner
Were the gas lines purged of air?
No
light?
Check inlet gas pressure. Is pressure correct?
Refer to page 13 for correct pressure for unit.
Yes
Check inlet gas shutoff. Adjust regulator.
Is the continuity of
Does the burner
No
the ground wire
stay on?
OK?
No
Yes
Repair wiring.
Does the burner
run until the call
Check the continuity of the ground wire.
No
for heat ends?
If a problem still exists, contact Enerco Group, Inc Technical Products
Customer Service 1-866-447-2194
Check Thermostat
and Wiring. Is the
Yes
power supply to unit
115V?
No
Find the source
of the electrical
problem
Is the air intake or
No
exhaust blocked?
Yes
Remove Obstruction
Check wiring and
No
connections
Is the ignitor
Yes
damaged?
No
Check voltage at
ignitor. Is it 1 15V
during ignition
cycle?
No
the LED indicator flashing two times.
No
Yes
Yes
Yes
Contact gas supplier
Are L1 and L2
Yes
No
reversed?
Yes
Repair wiring
Check the thermostat.
Enerco | Heatstar ERXL Series Heater
Remove door. Is
Is blower side door
Yes
voltage at door
in place?
switch 1 15V?
No
No
Check voltage at
Replace door
gas valve.
Check for 1 15V transformer input at plug
C3 on SmartValve. Check for 115V output
of C3. If no output voltage is present
replace SmartValve.
Check wiring and
Replace wiring and/
hose connection to
No
or hose connection.
air switch. Are they
OK?
Yes
Jumper wires at
Is the voltage at
pressure switch.
Yes
the transformer
Does the ignitor
secondary 24V?
glow red?
No
Is the voltage at the
transformer primary
Yes
Replace transformer
1 15V
Check LED indicator on SmartValve for
indication of fault. Refer to SmartValve testing
on page 21 to determine problem.
Replace ignitor.
No
Is the resistance
Check wire
Yes
through igniter 40
connections.
to 75 ohms?
The switch on the gas valve must be in the on
position and the line purged of air.
Check outlet gas pressure during ignition cycle.
Is the pressure 3.5" w.c. for natural or 10.5"
w.c. for lp?
No
Adjust to proper pressure.
Is the wiring at the
Is the insulation on
Yes
SmartValve OK?
the sensor lead OK?
No
No
Repair wiring
Repair wiring
A fault indication of six flashes may indicate
that the flame sensing circuit is not functioning
properly. Perform the following series of checks
to correct the problem.
E-21
Operating Instructions and Owner's Manual
Check door fit. If
Depress switch.
Yes
Yes
damaged, replace
Does blower come
on?
No
Check voltage to
No
Replace switch.
motor. Is it 1 15V?
Yes
Is the blower fan
Yes
Remove obstruction
obstructed?
No
Replace blower
motor.
Replace pressure
Yes
switch.
No
Replace SmartValve.
Are the wires to
No Replace/repair wires.
the SmartValve OK?
Yes
Replace SmartValve
Check for proper
Yes
burner orifice and
air plate.
Is the sensor
positioned
Repair/Replace
Yes
No
properly?
Yes
Is the sensor dirty?
Clean sensor.
Yes
No
Replace Sensor
door.
Yes