6. The device is now ready for operation. Press the
right key to start it and the left key to stop it.
Note:
After powering, the device outputs 0.00 mA or 0.00 V.
The Auto function does not start automatically.
Alter the manual start of the Auto function, the
device outputs the value ou.1. After the execution
of the cycle, the output remains with the value
ou.1.
4.2.3.1 The
in Auto Operating Mode
1. If YES was selected for
can show a value different from the value of the
output setpoint.
2.The SPecial disPlay function
A
The function SPecial.decimalPoint
–
allows defining the number of decimal places
(only for the values appearing on the display).
display.Low allows defining the
–
minimum value to be displayed.
display.High allows defining the
–
maximum value to be displayed.
SPecial disPlay Function
A
, the display
to
bei mA 24.00
to
bei mA 24.00
to
to
to
3. Press both keys to resume programming at point
4.2.3 (1), SiGn see
⇑
⇑
4. When outputting the setpoint in Auto mode,
when the SPecial disPlay function is activated,
the whole current or voltage ranges are used.
I.e. the setpoint ranges 0 ... 24 mA and 0 ... 12
V relate respectively to the scaled values.
If e.g. the value 5 is set for di.Lo and the value
10 is set for di.Hi, the current output will be set
as follows:
di.Lo 5 corresponds to 0 mA,
di.Hi 10 corresponds to 24 mA.
A
The scaled values must be used when inputting the
reference points (ou.1, ou.2, ... ). If the reference
point ou.1 is to output 12 mA (in the above examp-
to
le), you must input 7.5 and not 12 mA.
bei mA 24.00
to
4.2.4 Example of Auto Operating Mode
bei mA 24.00
Without Special display function
to
8 V
PE. 4
ou. 4
3 V
2 V
10 s 20 s 30 s 40 s 50 s
in the flow chart
A
PE. 5
ou. 5
EN - Page 9