The best way to program such a function is to set
up a table like the one opposite:
Example
PEr
ou. 1
0 V
PE. 1
5 s
ou. 2
3 V
PE. 2
5 s
ou. 3
2 V
PE. 3
10 s
ou. 4
3 V
PE. 4
10 s
ou. 5
3 V
PE. 5
10 s
ou. 6
8 V
PE. 6
10 s
ou. 7
8 V
PE. 7
10 s
ou. 8
0 v
PE. 8
5 s
EN - Page 10
Own values
8

5. Technical Data

Display
4-digit red 7-segment LED dis-
play, height 8 mm
Supply voltage: 10 ... 30 V DC, electrically isolated
Current consumption:
39 mA at 25°C, for a 20 mA
output current at 24 V DC
Power consumption:
max. 1 W
Test voltage:
500 V, 50 Hz., 1 min.
Test voltages:
EN 61010-1 for contamination
level 2 and
overvoltage category 2
EMC:
Interference emissions
EN 55011 Class B
Interference immunity
EN 61000-6-2
EN 61000-6-3
Operating temp.: -20 ... +65 °C, without condensation
Storage temp.:
-25 ... +85 °C, without condensation
Air humidity:
90% at 25 °C,
without condensation
Protection:
IP65 front
Weight:
approximately 50 g
Inputs:
2 front side keys for setting and
programming
Hold input, optocoupler, high active
low: 0 .. 2 VDC / high: 4 .. 30 VDC
Outputs:
Current output 0 ... 24 mA,
increment 10 µA
Load 20 mA up to ≤ 500 Ohms,
> 20 mA up to ≤ 400 Ohms
Ripple: <10 mVss
Voltage output 0 ..12 V,
increment 10 mV,
Load ≥ 2 kOhms, Ripple:
<10 mVss
Accuracy:
< 0,2 % of the upper range value
+ 0,02 %/K