CLEARANCE
For use on non-combustible countertops only.
Combustible and non-combustible material must be at least 48" (120cm) from the top of the
appliance and 6" (150mm) from the sides and back. Adequate clearance should also be provided
for proper operation and servicing.
AIR SUPPLY
Make certain not to obstruct the fl ow of combustion and ventilation air. Provisions for adequate
air supply must be furnished. The legs supplied with the unit must be installed. Make certain
that air intake openings in the bottom of the appliance are not obstructed. They are essential
for proper combustion and operation of the appliance.
EXHAUST CANOPY
It is essential that facilities be provided over the griddle to carry off fumes and gases. However,
the unit should not be directly connected to a fl ue or stack.
LEVELING UNIT
This griddle is supplied with (4) feet which must be screwed into the legs attached to the body.
Level unit by adjusting the (4) feet which have an adjustment of 1-3/4" (43.75mm) for accurate
and perfect lineup with other units.
DO NOT INSTALL WITHOUT ATTACHING FEET - DO NOT REMOVE FEET.
GAS PIPING
Gas piping shall be of such size and so installed as to provide a supply of gas suffi cient to
meet the full gas input of the appliance. If the appliance is to be connected to existing piping,
it shall be checked to determine if it has adequate capacity. Joint compound shall be used
sparingly and only on the male threads of the pipe joints. Such compounds shall be resistant to
the action of LP gases. WARNING: Any loose dirt or metal particles which are allowed to enter
the gas lines on this appliance will damage the valve and affect its operation. When installing
this appliance, all pipe and fi ttings must be free from loose dirt.
GAS PRESSURE REGULATOR
A convertible pressure regulator is provided with each griddle. It should be connected to the
inlet pipe at the rear of the unit. The gas supply line is then connected to it. It is shipped set for
6" (15.24cm) water column manifold pressure for use with natural gas.
MANUAL SHUT-OFF VALVE
A manual shut-off valve should be installed upstream from the union and within 6 feet (1.829m)
of this appliance.
PROPANE GAS
This griddle is equipped with fi xed orifi ce hoods and is shipped from the factory for use on
natural gas. To convert to propane gas, install the burner orifi ce hoods, located in the grease
drawer, as follows:
1. Remove front panel by removing screws located on the front and the bottom.
2. Remove the burner(s) from the orifi ce hood(s). This is accomplished by removing the
burner mounting screw(s) and sliding the burner(s) off the hood(s).
3. Remove natural gas orifi ce hood(s) and install the propane hood(s) furnished.
4. Reinstall burner(s).
Note: MD and TD series units use a #47 drill orifi ce for natural gas and a #55 drill orifi ce
for propane. TCHSD and TSPD series units (w/safety pilots) use a #41 drill orifi ce for
natural gas and a #52 drill orifi ce for propane gas.
5. Reinstall front panel.
CAUTION
6