Line Voltage Outputs
When using line voltage outputs directly from the IND560Dyn, the labeling
convention of O-
line voltage outputs. The diagnostic LED terminal blocks are not available for line
voltage outputs.
ARM100 Connections
With the exception of line voltage inputs, which must be isolated, all I/O points will
originate or terminate at the ARM100 terminals. Refer to the ARM100 Technical
Manual for further details.

Closing the Enclosure

To ensure that the IND9D56 provides continuous protection against the ingress of
moisture and dust, be sure the following steps are taken:
1. Ensure cord grips are appropriate for the outer diameter of the cable used.
2. If a cord grip is not being used, be sure to install a plug to prevent debris
3. When adding cable entrances, avoid placing them in the top surface of the
4. Be sure that the quarter-turn latch is completely engaged when the
n
will still be used. The terminal blocks used will be red to indicate
If there is too much gap, replace the cord grip with an appropriate grip
range.
from entering the enclosure.
enclosure. Whenever possible, the bottom of the enclosure is the preferred
location for cable entrances. Sides are the next best choice.
enclosure door is closed. Watch for field-installed cabling getting caught in
the door gasket. This can cause damage to the wire, and will also produce
gaps in the seal that allow moisture and debris into the enclosure.
IND9D56 Installation Manual
2-7