Technical Data
General Data
Operating mode:
Temperature range
operation:
storage :
altitude:
Clearance and creepage
distances
rated impuls voltage /
pollution degree:
EMC
Interference suppression:
Degree of protection
Housing:
Terminals:
Housing:
Vibration resistance:
Climate resistance:
Terminal designation:
Wire fixing:
Mounting:
Weight:
Dimensions
Width x height x depth:
UL-Data
The safety functions were not evaluated by UL. Listing is accom-
plished according to requirements of Standard UL 508, "general use
applications"
Nominal voltage U
:
N
Ambient temperature:
Switching capacity:
Ambient temperature 25°C
Ambient temperature 55°C:
Wire connection:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo
Standard Type
BG 5925.02/910/61 DC 24 V
Article number:
• Output:
• Nominal voltage U
:
N
• Width:
Ordering Example
BG 5925 . _ _ /910 /61 DC 24 V
Continuous operation
- 15 ... + 55 °C
- 25 ... + 85 °C
< 2.000 m
4 kV / 2 (basis insulation) IEC 60 664-1
IEC/EN 62 061
Limit value class B
EN 55 011
IP 40
IEC/EN 60 529
IP 20
IEC/EN 60 529
Thermoplastic with V0 behaviour
according to UL subject 94
Amplitude 0,35 mm IEC/EN 60 068-2-6
frequency 10 ... 55 Hz
15 / 055 / 04
IEC/EN 60 068-1
EN 50 005
Box terminal with wire protection,
removable terminal strips
DIN rail
IEC/EN 60 715
220 g
22,5 x 84 x 121 mm
DC 24 V
-15 ... +55°C
Pilot duty B300
5A 250Vac Resistive
5A 24Vdc Resistive or G.P.
Pilot duty B300
3A 250Vac Resistive
3A 24Vdc Resistive or G.P.
60°C / 75°C copper conductors only
AWG 20 - 12 Sol Torque 0.8 Nm
AWG 20 - 14 Str Torque 0.8 Nm
0049869
2 NO contacts
DC 24 V
22,5 mm
Nominal voltage
with UL-approval
Contact
Type
Troubleshooting
Failure
LED "Power" does not light up
LED "K1" lights up,
but "K2" remains off
LED "K2" lights up,
but "K1" remains off
Device cannot be activated
Maintenance and repairs
- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
15
Potential cause
Power supply not connected
- Safety relay K1 is welded
(replace device)
- A 1-channel switch-off occurred on
S12 (switch channel off on S22)
- Safety relay K2 is welded
(replace device)
- A 1-channel switch-off occurred on
S22 (switch channel off on S12)
- Safety relay K2 is welded
(replace device)
- Incorrect setting of switch S2
- Manual start mode:
Line fault on start-button (disconnect
power supply and remove fault)
- Automatic start mode:
S33-S34 not bridged
BG 5925/910 / 22.07.19 en / 148A