Unit Programming

Drawing shows setting at the state of delivery

Notes

Line fault detection on On-button:
The line fault detection is only active when S12 and S22 are switched
simultaneously. If The On-button is closed before S12, S22 is connected
to voltage (also when line fault across On-Button), the output contacts will
not close.
A line fault across the On-button which occurred after activation of the
relay, will be detected with the next activation and the output contacts
will not close. If a line fault occurs after the voltage has been connected
to S12, S22, the unit will be activated because this line fault is similar to
the normal On-function. The gold plated contacts of the BG 5925 mean
that this module is also suitable for switching small loads of 1 mVA - 7 VA,
1 mW - 7 W in the range 0,1 - 60 V, 1 - 300 mA. The contacts also permit
the maximum switching current. However since the gold plating will be
burnt off at this current level, the device is no longer suitable for switching
small loads after this.
The terminal S21 permits the operation of the device in IT-systems with
insulation monitoring, serves as a reference point for testing the control
voltage.
Connecting the terminal S21 to the protective ground bridges the internal
short-circuit protection of Line A2 (-). The short-circuit protection of line
A1 (+) remains active.
With the model BG 5925/910 control unit for safety mats, the switch S1
must always be set to cross fault monitoring. Depending on the operation
of the machine, the switch S2 is set to automatic or manual restart.

Technical Data

Input circuit
Nominal Voltage U
Voltage range
at 10% residual ripple:
Nominal consumption:
Min. Off-time:
Control voltage on S11:
plate
Max. permissible contact
resistance of safety mat:
Cross fault current
between line S11-S12 and
line S21-S22 with active
safety mat or safety edge
start-up:
continuously:
Control current over
S12, S22:
Min. voltage between
terminals S12, S22 and S21: DC 21 V when relay activated
Short-circuit protection:
Overvoltage protection:
Output
Contacts
BG 5925.02/910:
BG 5925.03/910:
BG 5925.16/910:
BG 5925.22/910:
The NO contacts are safety contacts.
The NC contacts 21-22 or 31-32 can only be used for monitoring.
Operate delay typ. at U
Manual start:
automatic start:
Release delay typ. at U
Disconnecting the supply:
Disconnecting S12, S22:
Contact type:
Nominal output voltage:
Switching of low loads:
(contact 5 µ Au)
Thermal current I
Switching capacity
to AC 15
NO contact:
NC contact:
to DC 13
NO contact:
NC contact:
to DC 13
NO contact:
NC contact:
Electrical contact life
to AC 15 at 2 A, AC 230 V:
to DC 13 at 1 A, DC 24 V:
Permissible operating
frequency:
Short circuit strength
max. fuse rating:
line circuit breaker:
Mechanical life:
14
:
DC 24 V
N
0,9 ... 1,1 U
N
DC approx. 2 W
1 s
approx. DC 23 V at U
30 Ω
max. 0,4 A for approx. 2 ms
40 mA at U
N
40 mA at U
N
and U
on A1 - A2
N
Internal fuse rating
Internal VDR
2 NO contacts
3 NO contact
1 NO, 1 NC contact
2 NO, 1 NC contact
:
N
80 ms
170 ms
:
N
50 ms
15 ms
forcibly guided
AC 250 V
DC: see arc limit curve
operation
≥ 100 mV
≥ 1 mA
:
5 A
th
(see current limit curve)
3 A / AC 230 V
1 A / AC 230 V
1 A / DC 24 V
1 A / DC 24 V
4 A / 24 V at 0.1 Hz
4 A / 24 V at 0.1 Hz
10
switching cycles IEC/EN 60 947-5-1
5
> 150 x 10
3
switching cycles
max. 1 200 operating cycles / h
6 A gG / gL
C 8 A
10 x 10
switching cycles
6
BG 5925/910 / 22.07.19 en / 148A
N
IEC/EN 60 947-5-1
IEC/EN 60 947-5-1
IEC/EN 60 947-5-1
IEC/EN 60 947-5-1
IEC/EN 60 947-5-1