(SyS Set up1 and SyS Set up2)
yStem
etup
This menu allows for the setting of BOOST MODE and NIGHT
MODE. BOOST MODE enables the system to operate at a
higher compressor speed than maximum compressor speed.
NIGHT MODE enables the system to operate at decreased
compressor and fan speeds.
BOOST MODE temperature can be adjusted in "BOOST
TEMP" menu. When ambient temperature gets higher than
BOOST MODE temperature, the system will operate in
BOOST MODE.
CHARGE MODE, DEFROST HEAT can be enabled within
this menu.
e
t
(equIp teSt)
quIpment
eSt
The mandatory system verification test is enabled from this
menu, which enables a functional check of the equipment, in
addition to ensuring proper stop valve position.
c
S
-
ool
et
up
This menu allows for the adjustment of several cooling per-
formance variables. "Cool Airflow Trim" (range from -15% to
+15% in 3% increments), "Cool Airflow Profiles", "Cool Fan
ON Delay", "Cool Fan OFF Delay" and "Dehumidification
Select" (enable or disable dehumidification) can be adjusted
in this menu. You can also reset this entire menu to factory
default settings. See the following images showing the four
cooling airflow profiles.
Profile A provides only an OFF delay of one (1) minute
at 100% of the cooling demand airflow.
100% CFM
OFF
Cooling Demand
Profile B ramps up to full cooling demand airflow
by first stepping up to 50% of the full demand for
30 seconds. The motor then ramps to 100% of the
required airflow. A one (1) minute OFF delay at 100%
of the cooling airflow.
100% CFM
50% CFM
OFF
1/2 min
Cooling Demand
Profile C ramps up to 82% of the full cooling demand
airflow and operates there for approximately 7 1/2 minutes.
The motor then steps up to the full demand airflow. Profile
C also has a one (1) minute 100% OFF delay.
82% CFM
OFF
7 1/2 min
Cooling Demand
100% CFM
OFF
1 min
100% CFM
OFF
1 min
100% CFM
100% CFM
OFF
1 min
Profile D (default) ramps up to 50% of the demand
for 1/2 minute, then ramps to 82% of the full cooling
demand airflow and operates there for approximately
7 1/2 minutes. The motor then steps up to the full
demand airflow. Profile D has a 1/2 minute at 50%
airflow OFF delay.
82% CFM
OFF
50% CFM
1/2 min
7 1/2 min
Cooling Demand
See service manual for more detailed information.
c
r
V
ool
un
alueS
Depending on the system configuration, adjusting the maxi-
mum compressor RPS (revolutions per second) may be re-
quired. Necessary adjustments to the maximum compressor
RPS are made through the following sub-menus.
c
rpS r
ool
ange
→ m
c
axImum
ompreSSor
Select the range that your maximum compressor RPS
falls within.
c
rpS S
ool
elect
→ m
c
axImum
ompreSSor
Within the selected range, choose the specific maximum
compressor RPS for the system configuration.
noTE: Under high ambient, the unit may ramp down com-
pressor RPS by protection, even max RPS is changed higher
by this menu.
It may be under Compressor Reduction Mode.
57