Daikin DZ17VSA Instructions D'installation page 59

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

SUBMENU ITEM
Reset System Setup Options to
Factory Defaults (SYS SETUP
RESET)
SET MAX CURRENT
VERTICAL RISE
BOOST MODE ("BOOST MD")
BOOST MODE TEMPERATURE
(BOOST TEMP)
DEFROST HEAT (DF HEAT)
CHARGE MODE
NIGHT MODE (NIGHT MD)
NOISE DOWN LEVEL
NIGHT MODE START
NIGHT MODE END
CAPACITY PRIORITY
(CAP PRIORITY)
SUBMENU ITEM
System Verification Test
(SYSTEM TEST)
SYSTEM SETUP (SYS SETUP1 and SYS SETUP2)
USER MODIFIABLE OPTIONS
NO or YES
N/A
Same Level (Same LV), Outdoor
Lower (OD Low), or Indoor Lower
(ID Low)
ON or OFF
Always ON, 70, 75, 80, 85, 90,
95, 100, 105°F
Always ON, 30, 35, 40, 45, 50,
55, 60, 65°F, OFF
ON or OFF
ON or OFF
1, 2, or 3
-2Hour, -1Hour, Standard,
+1Hour, +2Hour
-2Hour, -1Hour, Standard,
+1Hour, +2Hour
ON or OFF
EQUiPMEnT TEST (EQUiP TEST)
INDICATION/USER MODIFIABLE
OPTIONS
ON or OFF
59
59
COMMENTS
Selecting "YES" resets this menu to factory de-
fault settings.
Future use.
If the outdoor & indoor units are within +/- 15 ft.
vertical distance, select "SAME LEVEL". If the out-
door unit is more than 15 ft. below the indoor unit,
select "OUTDOOR LOWER". If the outdoor unit
is more than 15 ft. above the indoor unit, select
"INDOOR LOWER".
"BOOST MD" turns BOOST MODE OFF or ON.
BOOST MODE is ON by default. See BOOST
MODE section of this manual for more details.
BOOST TEMP adjusts the activation temperature
from 70°F to 105°F. An "Always ON" option is also
available to permanently engage BOOST MODE.
DEFROST HEAT is OFF by default. See
DEFROST HEAT section of this manual for more
details.
Enter Charging Mode. This allows for a steady
system operation for a duration of approximately
1 hour to allow for refrigerant charging of the sys-
tem via the suction charge port. The system will
stop after completion.
NIGHT MODE is OFF by default. See NIGHT
MODE section of this manual for more details.
NOISE DOWN LEVEL adjusts the noise level. 3 is
the most quiet level.
NIGHT MODE START adjusts the time to start for
NIGHT MODE.
NIGHT MODE END adjusts the time to end for
NIGHT MODE.
CAP PRIORITY is ON by default. If during operation
the capacity demand is high, then the night mode
function will be temporarily overridden by the cap
priority function to return the room temperature to
the set point.
COMMENTS
System Verification Test must be run after installa-
tion. This is approximately a 10-15 minute test. If
the thermostat is set to COOL mode, the system
will enter CHARGE mode upon completion, other-
wise it will stop.

Publicité

Table des Matières
loading

Table des Matières