Activation test
ENG
48
27
Activation test
In order to perform the test, the devices have to be
correctly programmed for each other and the actuator
(receiver) must be set to mode "S" (standard) or "R"
(repeater).
Set the selector switch to "T". The Watchdog is now in
testing mode for 10 minutes (daytime operation, light-on
time 5 sec.). In addition, each detection is indicated by the
status LED flashing quickly (Adjustments, pos. 1).
Then the Watchdog automatically switches over to the
"group control" mode with a normal sensitivity and
"nightfall" brightness threshold (see Operation).
To perform another activation test, set the selector switch
to another position than "T" and then back to "T". The
Watchdog is now for another 10 minutes in the testing
mode.
Testing mode exit: Automatically after 10 minutes or by
selecting another operating mode.