Technical Specifications; General Features - sauermann CP 110 Guide De Démarrage Rapide

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Quick Start Guide
English
Features
0-10 V or 4-20 mA output, active, power supply
24 Vac/Vdc (3-4 wires) or 4-20 mA output, passive
loop, power supply from 16 to 30 Vdc (2 wires)
ABS V0 housing, IP65, with or without display

General features

Output / Supply
Consumption
European directives
2014/30/EU EMC; 2014/35/EU Low Voltage; 2011/65/EU RoHS II; 2012/19/EU WEEE
Electrical connection
PC Communication
Environnement
Response time
Zero setting
Manual autozero with push-button; self-calibration by solenoid valve (CP 111 only)
Type of fluid
Conditions of use
(°C/%RH/m)
Storage temperature
*All the accuracies indicated in this technical datasheet were stated in laboratory conditions, and can be guaranteed for measurements carried out in the same conditions, or carried out with calibration compensation.
Differential pressure
transmitter
Ranges from -500/+500 Pa to
-10 000/+10 000 Pa (according to model)
Configurable intermediary
ranges
"¼ turn" system mounting with wall-mount plate
Housing with simplified mounting system
Solenoid valve for auto-calibration (only on
CP 111 model)
Active sensor 0-10 V or 4-20 mA (alim. 24 Vac/Vdc ±10%), 3-4 wires
Passive loop 4-20 mA (power supply 16/30 Vdc), 2 wires
Common mode voltage <30 VAC
Maximum load: 500 Ω (4-20 mA) / minimum load: 1 K Ω (0-10 V)
CP 111: 3 VA (0-10 V) or 3 VA (4-20 mA)
CP112, CP113, CP 114, CP 115: 2 VA (0-10 V) or 0.6 VA (4-20 mA)
Screw terminal block for cables from 0.05 to 2.5 mm
or from 30 to 14 AWG
2
Carried out according to the code of good practice
USB-mini DIN cable
Air and neutral gases
1/e (63%) 0.3 s
Air and neutral gases
From 0 to +50 °C. In non-condensing condition. From 0 to 2000 m
From -10 to +70 °C

Technical specifications

CP 111
CP 112
Measuring ranges
-100/+100 Pa
-1000/+1000 Pa
Pa, mmH
O,
Pa, mmH
O,
2
2
Measurement
inWG, mmHG,
inWG, mmHG,
units
daPa, kPa, hPa,
daPa, kPa, hPa,
mbar
mbar
±1% of reading
±1.5% of reading
Accuracy*
±2 Pa
±3 Pa
1 Pa;
1 Pa;
0.1 mmH
O;
0.1 mmH
O;
2
2
0.01 mbar;
0.01 mbar;
0.01 inWG;
0.01 inWG;
Resolution
0.01 mmHG;
0.01 mmHG;
0.1 daPa;
0.1 daPa;
0.001 kPa;
0.001 kPa;
0.01 hPa
0.01 hPa
Overpressure
21 000 Pa
21 000 Pa
tolerated
Features of the housing
Material
Protection
Display
Height of digits: values: 10 mm; units: 5 mm
Connections
Cable gland
Weight
46 mm
Symbols used
For your safety and in order to avoid any damage of the device, please follow the procedure described in
this document and read carefully the notes preceded by the following symbol:
The following symbol will also be used in this document, please read carefully the information notes
indicated after this symbol:
CP 113
CP 114
CP 115
-10 000 /+10 000 Pa
-500/+500 mbar
-2000/+2000 mbar
Pa, mmH
O,
mbar, inWG,
mbar, inWG,
2
inWG, mmHG,
mmHG, PSI,
mmHG, PSI,
daPa, kPa, hPa,
mmH
O, daPa,
mmH
O, daPa,
2
2
mbar
hPa, kPa
hPa, kPa
±1.5% of reading
±3% of reading
±3% of reading
±30 Pa
±50 ppm
±50 ppm
1 Pa;
1 mbar;
1 mbar;
0.1 mmH
O;
0.1 inWG;
0.1 inWG;
2
0.01 mbar;
1 mmHG;
1 mmHG;
0.01 inWG;
1 mmH
O;
1 mmH
O;
2
2
0.01 mmHG;
1 hPa;
1 hPa;
0.1 daPa;
10 daPa;
10 daPa;
0.01 kPa;
0.1 kPa;
0.1 kPa;
0.01 hPa
0.1 PSI
0.1 PSI
69 000 Pa
1400 mbar
4100 mbar
ABS V0 as per UL94
IP65
LCD 10 digits.
Dimensions: 50 x 17 mm
Ribbed, Ø 6.2 mm
For cables Ø 8 mm maximum
143 g
90 mm