4. Go to the R7999C ControLinks and press the Reset
button. As it turns on the different LEDs, press the
"Enter" command on the Commission screen to enter
the password. You should be into the setup screen. If
the R7999C Alarms again, you may need to repeat
the above steps.
5. You cannot enter ControLinks commissioning while it
is in Alarm.
6. Once you have entered the Commission screen,
return to the replaced actuator and reconnect the
Red connector.
7. Return to the commissioning process by entering the
new actuator and setting up the end points.
8. Reload the profile curve and verify the curve.
15
R7999C CONTROLINKS™ CONTROLLER
32-00081EF—01