Klein Tools CL440 Manuel D'utilisation page 11

Multimètre à pince cvc
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Apply test leads to the circuit to be tested to measure voltage.
The meter will auto-range to display the measurement in the most
appropriate range.
NOTE: If "–" appears on the LCD, the test leads are being applied to
the circuit in reverse. Swap the position of the leads to correct this.
NOTE: To access mV range for V AC , the 'RANGE' button
be used.
Manual Mode Sequence
AC Range
0-750V
DC Range 0-60.00V 0-6.000V 0-600.0mV 0-600.0V 0-60.00V
NOTE: When in a voltage setting and the test leads are open,
readings of order mV may appear on the display. This is noise and
is normal. By touching the test leads together to close the circuit
the meter will measure zero volts.
INRUSH CURRENT
The Inrush feature captures starting current of a motor or transformer.
Starting current can assist in diagnosing a motor before it fails.
To measure inrush current:
1. Rotate the Function Selector switch
2. Place clamp
shown in the main display.
3. Press the InRush button
to enter the Inrush mode and manually
select 60A or 600A range
by pressing the RANGE button
Place the clamp around the compressor
start wire and turn motor on. The
starting current will hold on the main
display. The Inrush measurement period
is 100-miliseconds. The secondary
display measures running current.
4. Press InRush button
OPERATING INSTRUCTIONS
First
Second
Press
Press
0-600.0V 0-60.00V 0-6.000V 0-600.0mV
around wire. The current measurement will be
3
17
to exit.
17
Third
Press
2
to the AC current A
.
7
7
Fourth
Fifth
Press
Press
setting.
must
11

Publicité

Table des Matières
loading

Table des Matières