Macurco TX-6-ND Instructions D'utilisation page 8

Détecteur de dioxyde d'azote, contrôleur et transducteur
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

8.
The Fan Relay can be configured for latching or non-latching (default) when activated (when the gas concentration exceeds fan
relay set point). Once latched in, power will need to be interrupted or the "TEST" button pressed to un-latch the relay condition.
9.
The Fan Relay will engage if the fan setting Nitrogen Dioxide concentration is exceeded for longer than the Fan Relay Delay
time. Unless it is configured for latching, the fan relay will disengage once both of these conditions have been met:
Nitrogen Dioxide concentration has dropped below fan setting
Fan Relay Run time has been exceeded
Note that the "disable" fan setting will cause the fan relay to not engage. The fan relay will engage in trouble fault condition (if
the Trouble Fan Setting Option is set to "ON") and will disengage once trouble fault condition is cleared.
10.
The Current Loop is 4 mA in clean air and 20 mA for 20 ppm Nitrogen Dioxide
8

Publicité

Table des Matières
loading

Table des Matières