Features; Specifications; Installation And Operating Instructions - Macurco TX-6-ND Instructions D'utilisation

Détecteur de dioxyde d'azote, contrôleur et transducteur
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Features

ETL Listed to UL 61010-1 and CAN/CSA C22.2 No 61010-1
Low level meter capable of displaying from 0-20 ppm Nitrogen Dioxide
The TX-6-ND meets Uniform Building Code for enclosed garages and OSHA standards for gas exposure
Selectable fan and alarm relay activation
5 A SPDT fan relay controls starters of exhaust fans
0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
4-20 mA Current Loop
TX-6-ND mounts on a standard 4x4 electrical box and becomes cover for the box
Supervised system: any internal detector problem will cause the fan & alarm relay to activate
Calibration kit is available. One screw allows access for calibration or gas test

Specifications

Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC
Current @ 24 VDC: 75 mA in alarm (two relays), 50 mA (fan relay only) and 23 mA stand by
Shipping Weight: 1 pound (0.45 kg)
Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 10.2 X 5.4 cm)
Color: Dark gray
Connections: plugs/terminals
Mounting box: (not included) 4x4 electric
Fan relay: 5 A, 240 VAC, pilot duty, SPDT
Fan relay actuation: selectable at dIS (disabled) 0.5, 0.7, 1.0, 1.2, 1.5, 1.7, 2.0, 2.2, 2.5 (default), 2.7, 3.0, 3.2, 3.5, 3.7,
4.0, 4.2, 4.5, 4.7, 5.0 ppm
Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
Fan Minimum Run Time settings are 0 (default), 3, 5, 10 or 15 minutes
Fan relay latching or not latching (default) selectable
Alarm relay: 0.5A 120 V, 60 VA
Alarm relay actuation: selectable N.O. (default) or N.C.
Alarm relay settings: dIS, 1, 2, 3, 4, 5 (default), 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20 ppm
Current Loop: 4-20 mA for 0-20ppm NO
Buzzer: 85 dBA at 10cm settable to off (default) or on
Digital display: 3 digit LED selectable to off (default) or on
Operating Environment: 0 ° F to 125 ° F (-18 ° C to 52 ° C). 10 to 90% RH noncondensing

INSTALLATION AND OPERATING INSTRUCTIONS

The following instructions are intended to serve as a guideline for the use of the Macurco TX-6-ND Nitrogen Dioxide Detector. It is not
to be considered all-inclusive, nor is it intended to replace the policy and procedures for each facility. If you have any doubts about the
applicability of the equipment to your situation, consult an industrial hygienist or call Technical Service at 1-877-367-7891.
selectable to off (default) or on
2,
6

Publicité

Table des Matières
loading

Table des Matières