Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

AEV Series
Air Exchanger Ventilator
PARTS IN THE BOX
Air Exchanger, 1 pc
Hanging Bracket, 2 pcs
MDEH1 Dehumidistat, 1 pc
Operation and Installation Manual, 1 pc
Your ventilation system should be installed in conformance with the appropriate provincial requirements or, in the absence of
such requirements, with the current edition of the National Building Code, and / or ASHRAE's "Good Engineering Practices".
United States
10048 Industrial Blvd., Lenexa, KS, 66215
Tel.: 800.747.1762 • Fax: 800.487.9915
Canada
50 Kanalflakt Way, Bouctouche, NB, E4S 3M5
Tel.: 800.565.3548 • Fax: 877.747.8116
Fantech reserves the right to modify, at any time and without notice, any or all of its products' features, designs,
components and specifications to maintain their technological leadership position.
Please visit our website www.fantech.net for more detailed technical information.
Installation Manual
Item #: 401334
Rev Date: 2019-11-19

Publicité

Chapitres

Table des Matières
loading

Sommaire des Matières pour SystemAir Fantech AEV Serie

  • Page 1 Item #: 401334 Rev Date: 2019-11-19 Installation Manual AEV Series Air Exchanger Ventilator PARTS IN THE BOX Air Exchanger, 1 pc Hanging Bracket, 2 pcs MDEH1 Dehumidistat, 1 pc Operation and Installation Manual, 1 pc Your ventilation system should be installed in conformance with the appropriate provincial requirements or, in the absence of such requirements, with the current edition of the National Building Code, and / or ASHRAE’s “Good Engineering Practices”.
  • Page 2 Note Warning/ Information Technical Practical tip Important note information Note Avertissement/ Information Information Conseil Note importante technique pratique PLEASE READ THIS MANUAL VEUILLEZ LIRE LE MANUEL AVANT BEFORE INSTALLING UNIT D’INSTALLER L’APPAREIL Products are designed and manufactured to provide Les produits sont conçus et fabriqués pour fournir une reliable performance, but they are not guaranteed performance fiable, mais ils ne sont pas garantis à...
  • Page 3: Table Des Matières

    Table of content DETERMINING YOUR AIRFLOW REQUIREMENT ........... . . 4 OPERATION .
  • Page 4: Determining Your Airflow Requirement

    Determining your airflow requirement Room Count Method Room classification Number of rooms CFM (L/s) CFM Required Master bedroom x 10 L/s (20 CFM) if yes add 10 L/s (20 CFM) Basement yes or no if no = 0 Bedrooms x 5 L/s (10 CFM) Living room x 5 L/s (10 CFM) Others...
  • Page 5: Operation

    Operation A Air Exchangers (AEV) is designed to bring fresh air into a building while exhausting an equal amount of stale air. During the winter months, the incoming cold fresh air is warmed by utilizing the heat recovered from the stale air before it is exhausted to the outdoors. During summer months when the indoor space is air conditioned, the AEV will help in cooling the incoming fresh air with the stale air that is being exhausted.
  • Page 6: Installation Examples

    Installation examples Example only RADIANT, HYDRONIC AND ELECTRIC BASEBOARD HEATING This diagram shows the installation of your unit with radiant hydronic or baseboard heating. As shown, the stale air is extracted from the rooms with high humidity levels, and the fresh air is delivered in the living areas. In this case, a complete ducting system for ventilation must be installed.
  • Page 7: Exterior Ducting Installation

    Exterior ducting installation A well designed and installed ducting system will allow the AEV to operate at OUTSIDE CORNER INSIDE CORNER its maximum efficiency. Always try to keep duct runs as short and straight as 36" (1m) 36” (1m) possible. min.
  • Page 8: Interior Ducting Installation

    Interior ducting installation Exhaust air ducting The stale air exhaust system is used to draw air from the points in the house where the worst air quality problems occur. It is recommended that return air ducts be installed in the bathroom, kitchen, and laundry room. Additional return air ducts from strategic locations (i.e. greenhouse, atrium, swimming pool, sauna, etc.) may be installed.
  • Page 9: Aev Installation

    AEV installation Location The Air Exchanger must be located where it will be possible to conveniently service the unit. Typically the AEV would be located in an area close to the outside wall where the weatherhoods will be mounted. If a basement area is not convenient or does not exist, a utility or laundry room may be used.
  • Page 10: Airflow Balancing

    Airflow balancing The balancing procedure consists of measuring the exhaust air leaving the system and the supply air entering the system and ensuring that these two are equal. A deviation of 10% or less is acceptable. In such cases, it is recommended to have a greater amount of exhaust air than supply air as so to increase the supply air’s temperature.
  • Page 11: Pitot Tube Balancing Procedure

    Airflow balancing (Cont'd) 1 For this flow measuring station, cut the duct 2 Before taking the reading, make sure that 3 The airflow is regulated by a balancing and place the flow measuring station the magnehelic gauge is level and at 0. damper.
  • Page 12: Maintenance

    Pitot tube balancing procedure (Cont'd) Place pitot tube a min. of 18" from blower or elbows Outdoors To House Magnehelic gauge Pitot Tube Pitot Tube From house Magnehelic gauge Duct connections may vary, depending on model. Pitot tube should be kept at least 12” away from fans elbows and dampers to ensure accurate reading. Maintenance Make sure unit is unplugged before attempting any maintenance work.
  • Page 13: Wiring Diagram

    Wiring diagram NEUTRAL LINE...
  • Page 14: Troubleshooting

    Troubleshooting Problem Causes Solutions Air is too dry Dehumidistat control is set too low Increase the desired level of humidity. Change ventilation mode from continuous mode to standby. AEV out of balance Balance AEV Air is too humid Dehumidistat control is set too high Reduce the desired level of humidity.
  • Page 15: Aev Maintenance Chart

    AEV maintenance chart Limited Warranty • The motor found in all units require no lubrication, and are factory Maintenance Required Recommended Frequency Date Maintenance Performed balanced to prevent vibration and Check and Clean Filters Every 3 months or if promote silent operation. dirty •...
  • Page 16 Notes...
  • Page 17 No. d'article: 401334 Date de révision: 2019-11-19 Manuel d'installation Série AEV Ventilateur d'échangeur d'air PIÈCES DANS LA BOÎTE Ventilateur d'échangeur d'air, 1 pc Support muraux, 2 pcs MDEH1 Déshumidistat, 1 pc Manuel d'installation, 1 pc Votre système de ventilation doit être installé conformément aux exigences de la province où vous habitez ou, à défaut de telles exigences, conformément à...
  • Page 18 Table des matières DÉTERMINER VOS BESOINS DE VENTILATION ........... . . 19 OPÉRATION .
  • Page 19: Déterminer Vos Besoins De Ventilation

    Déterminer vos besoins de ventilation Méthode compte de pièces Pi 3 /min (L/s) Liste des pièces Nombre de pièces PCM Required x 10 L/s (20 pi 3 /min) Chambre principale 3 /min Si oui, ajoutez 10 L/s (20 pi Sous-sol oui ou no Sinon = 0 x 5 L/s (10 pi 3 /min)
  • Page 20: Opération

    Opération Un échangeur d'air (EA) assure un apport d’air frais dans le bâtiment tout en évacuant une quantité égale d’air vicié. Durant les mois d’hiver, l’air froid entrant est chauffé par la chaleur récupérée de l’air vicié avant que celui-ci soit évacué. En été, lorsque l’intérieur est climatisé, le EA utilise l’air vicié évacué...
  • Page 21: Exemples D'installation

    Exemple d'installation Exemple seulement Élément chauffant, Hydronic et chauffage électrique de baseboard Ce diagramme montre l'installation de votre unité avec le chauffage radiant hydronic ou de baseboard. Comme montré, l'air éventé est extrait à partir des salles avec des niveaux de humidité élevé, et l'air frais est livré dans les secteurs vivants.
  • Page 22: Installation Des Conduits Extérieurs

    Installation des conduits extérieurs Coin extéreur Coin intérieur OUTSIDE CORNER INSIDE CORNER Le rendement maximum du EA est assuré par un ensemble de conduits 36po (1m) 36po (1m) d’évacuation de haute qualité technique qui est bien installé. Assurez-vous que le 36"...
  • Page 23: Installation Des Conduits Intérieurs

    Installation des conduits intérieurs Ensemble de conduits d’évacuation Le système d’évacuation de l’air vicié sert à aspirer l’air des endroits de la maison où la qualité d’air est la moins bonne. Il est recommandé d’installer les conduits de retour d’air dans la salle de bains, la cuisine et la buanderie. Il est également possible d’installer des conduits supplémentaires de retour d’air dans des endroits stratégiques (p.
  • Page 24: Installation De L'ea

    Installation de l'EA Emplacement Le EA doit être situé dans un endroit chauffé où il sera possible d’en effectuer la maintenance sans inconvénient. Généralement, le EA doit être situé dans la chambre des appareils mécaniques ou à proximité du mur extérieur sur lequel les hottes de protection contre les intempéries seront montées.
  • Page 25: Équilibrage Du Débit D'air

    Équilibrage du débit d'air Le procédé d'équilibrage se compose mesurer l'air d'échappement partant du système et l'air d'approvisionnement écrivant le système et s'assurant que ces deux sont égales. Une déviation de 10% ou moins est acceptable. Dans ces cas-ci, on lui recommande d'avoir une plus grande quantité d'air d'échappement que fournir l'air en tant qu'ainsi pour augmenter la température d'air d'approvisionnement.
  • Page 26: Équilibrage Du Débit D'air (Suite)

    Équilibrage du débit d'air (Suite) 1 Pour ce poste de mesure des débits, coupez 2 Avant de prendre la lecture, assurez-vous que 3 Le débit d’air est régulé à l’aide d’un registre le conduit et placez le poste entre chaque le manomètre Magnehelic est de niveau et d’équilibrage situé...
  • Page 27: Procédure D'équilibrage À L'aide D'un Tube De Pitot (Suite)

    Procédure d'équilibrage à l'aide d'un tube de pitot (Suite) Placez le tube de Pitot à au moins 18 po du ventilateur ou des coudes. Extérieur À la maison Manomètre Magnehelic Tube de Pitot Tube de Pitot Manomètre De la maison Magnehelic Les raccords de conduit peuvent être différents selon le modèle.
  • Page 28: Schéma Électronique

    Schéma électronique NEUTRAL LINE...
  • Page 29: Dépannage

    Dépannage Problème Causes Solutions L’air est trop sec – Le déshumidistat est réglé trop bas – Augmentez le niveau voulu d’humidité. Faites passer le mode de ventilation de « continu » à « attente ». – Le VRC est déséquilibré –...
  • Page 30: Tableau D'entretien Du Ea

    Tableau d'entretien du EA La meilleure garantie limitée sur le marché • Le noyau récupérateur de chaleur Entretien requis Fréquence recommandée Date de l'entretien en polypropylène bénéficie d’une garantie à vie limitée. Vérifiez et nettoyez les à chaque 3 mois, ou s'ils filtres sont sales •...
  • Page 31: Liste Des Composantes

    Parts list • Liste des composantes AEV1000 BOM # Description (40146) Collar 5” 410529 Motor Assembly 405520 Synt. Filter 40187 Control Switch 410212 2 Pos. Terminal 401059 Auto-Transformer 422710 Capacitor, 6uF 411222 Relay Board 410364...
  • Page 32 Fantech reserves the right to make technical changes. Fantech se réserve le droit de faire des changements tech- For updated documentation please refer to www.fantech.net niques. Pour de la documentation à jour, s'il vous plaît se référer au www.fantech.net Fantech®...

Ce manuel est également adapté pour:

Aev100040146

Table des Matières