3-way connection
of drainage pipe joint
Fig.24
5.4.3 Precautions When Doing Riser Piping Work
(1). Make sure that heat insulation work is executed on the following 2 spots to prevent any
possible water leakage due to dew condensation.
1). Connect the drain hose to the drain lift pipe, and insulate them.
2). Connect the drain hose to the drain outlet on the indoor unit, and tighten it with the clamp.
(4). Secure a downward gradient of 1/100 or more for the drain pipe. To accomplish this, mount
supporting brackets at an interval of 1 -1.5 m.
(Correct) 1/100 or more gradient
(5). The incline of attached drain hose should be 75 mm or less so that the drain outlet does not
have to withstand additional force.
DC Inverter Free match Series Cassette Type Unit
Connection of drain elbow
Fig.25
Fig.27
1-1.5m
Fig.28
Fig.29
24
Connection of horizontal pipe
Fig.26
Drain lift pipe
×
(wrong)