Connection to power supply

The socket should be connected in compliance with the relevant standard, to a dedicated
omnipolar circuit breaker. 25 A minimum supply.
Monophase 230V~ 1P+N
Put a bridge between terminal 1 and 2
Attach the green/yellow wire to the terminal Earth
The neutral N to the terminal 4
The phase L to one of the terminal 1 or 2
Biphase 400V~ 2P+N
Attach the green/yellow wire to the terminal Earth
The neutral N to the terminal 4
The phase L1 to the terminal 1 and the phase L2 to the terminal 2
Mains
230~ 50/60Hz
400V~ 50/60Hz
* calculated with the simultaneous factor following standard EN 60 335-2-6
Caution!
Tightening the screws too much can damage the screw thread. It is therefore
advisable to keep screwing and unscrewing to a minimum.
Ensure that the cables are correctly inserted and tightly screwed down.
We cannot be held responsible for any incident resulting from incorrect connection or
which could arise from the use of an appliance which has not been earthed or has been
Connection
Cable diameter
1 Phase + N
3 x 2,5 mm
2 Phase + N
4 x 1,5 mm
equipped with a faulty earth connection.
Cable
H 05 VV - F
2
H 05 RR - F
H 05 VV - F
2
H 05 RR - F
34
Protection calibre
25 A *
16 A *