Figure 10 Securing the wires to the terminals
Method 1
a.
G
L
N
7. Connect the AC supply wiring from the charger to the AC
panel feeding the charger.
8. Connect the line conductor to the breaker, the neutral to the
neutral bus, and the ground to the ground bus. In Canada
and the USA, an external junction box is required between
the AC circuit breaker and the charger.
Figure 11 AC supply wiring
975-1023-01-01
Method 2
b.
G
L
N
9. Secure cables in place using tie-wraps or cable straps
according to electrical codes.
10. Replace the wiring strain-relief bar and attach the screws to
secure the wires and cables.
ELECTRICAL SHOCK HAZARD
Use a torque screwdriver to tighten the wiring strain relief bar
screws to 6.687 in-lbs (0.755 N-m) torque to ensure a required tool
access to the wiring compartment.
Failure to follow these instructions can result in death, serious
injury, or equipment damage.