Mechanical Specifications; Electrical Specifications; Electromagnetic Compatibility - Chauvin Arnoux PAC 11 Notice De Fonctionnement

Pince ampèremétrique
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

4.4. MECHANICAL SPECIFICATIONS

- Watertightness :
- Clamping diameter : 1 cable ∅ 30 mm (or 2 cables ∅ 24 mm)
- Outside dimensions of clamp : 224 x 97 x 44 mm
- Fitted lead :
- Weight :
- Drop height :
- Protection from shocks : 100 g in accordance with IEC 68-2-27
- Vibrations :

4.5. ELECTRICAL SPECIFICATIONS

- Power supply :
- Battery life :
Operating limits
On DC current :
On AC :
The maximum permitted current (AC) on overload from 1 kHz is defined in accordance with the following
formula :
1000
Ip max =
F(kHz)
Electric shocks
Instrument with dual insulation or strengthened insulation in accordance with IEC 61010-2-032.
Between the primary, the secondary and the hand-held part located below the guard, dielectric test
voltage: 7850 V DC
Maximum common mode voltage between the conductor on which the measurement is made and the
earth, or the output and the earth:
- 600 V for installations of category III and degree of pollution 2
Installation category and degree of pollution in accordance with IEC 664 and 664A

4.6. ELECTROMAGNETIC COMPATIBILITY

Emissions and immunity in an industrial setting compliant with IEC 61326-1.
IP 30 in accordance with IEC 529
a busbar of cross section 50 x 10 mm
1.5 m
440 g approx
to IEC 68-2-32
to IEC 68-2-6
9 V battery (type 6LR61, 6LF22 or NEDA 1604)
approx 50h with an alkaline battery
3000 A permanent
1000 A permanent up to 1 kHz
15