Electrical Work - Mitsubishi Electric Mr.SLIM PUHZ-RP HA2 Serie Manuel D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 20

6. Electrical work

6.1. Outdoor unit (Fig. 6-1, Fig. 6-2)
(1) Remove the service panel.
(2) Wire the cables referring to the Fig. 6-1 and the Fig. 6-2.
For Heater
For Power
For Heater
For Heater
For Power
6.2. Field electrical wiring
Outdoor unit model
Outdoor unit power supply
Outdoor unit input capacity
Main switch (Breaker)
Outdoor unit power supply
Outdoor unit power supply earth
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Remote controller-Indoor unit
Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
Remote controller-Indoor unit
*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
*2. Max. 45 m
If 2.5 mm
used, Max. 50 m
2
If 2.5 mm
used and S3 separated, Max. 80 m
2
*3. The 10 m wire is attached in the remote controller accessory.
*4. The figures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.
Notes: (1) Wiring size must comply with the applicable local and national code.
(2) Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
(3) Install an earth longer than other cables.
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power
line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power
is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-poles type.
8
* W ith Heater
model only
(A) Indoor unit
(B) Outdoor unit
(C) Remote controller
(D) Main switch (Breaker)
(E) Earth
For Heater
Fig. 6-1
RP35, 50V
~/N (single), 50 Hz,
*1
2 × Min. 1.5
1 × Min. 1.5
*2
3 × 1.5 (Polar)
*2
1 × Min. 1.5
*3
2 × 0.3 (Non-polar)
*4
AC 230 V
*4
AC 230 V
*4
*4
230V
Single phase
Isolator
A-Control
Outdoor Unit
n RP35, 50V
n RP60-140
(A) Earth terminal
(B) Terminal block
(C) Clamp
(D) Service panel
(E) Wire the cables so that they do
not contact the center of the
service panel or the gas valve.
RP60, 71V
~/N (single), 50 Hz,
230 V
230 V
16 A
25 A
2 × Min. 2.5
1 × Min. 2.5
3 × 1.5 (Polar)
1 × Min. 1.5
2 × 0.3 (Non-polar)
AC 230 V
AC 230 V
DC 24 V
DC 24 V
DC 12 V
DC 12 V
3 poles isolator
n RP60-140V
n RP100-140Y
Fig. 6-2
RP100, 125V
RP140V
~/N (single), 50 Hz,
~/N (single), 50 Hz,
230 V
230 V
32 A
40 A
2 × Min. 4
2 × Min. 6
1 × Min. 4
1 × Min. 6
3 × 1.5 (Polar)
3 × 1.5 (Polar)
1 × Min. 1.5
1 × Min. 1.5
2 × 0.3 (Non-polar)
2 × 0.3 (Non-polar)
AC 230 V
AC 230 V
AC 230 V
AC 230 V
DC 24 V
DC 24 V
DC 12 V
DC 12 V
A-Control
Indoor Unit
RP100, 125, 140Y
3N ~ (3phase), 50 Hz,
400 V
16 A
4 × Min. 1.5
1 × Min. 1.5
3 × 1.5 (Polar)
1 × Min. 1.5
2 × 0.3 (Non-polar)
AC 230 V
AC 230 V
DC 24 V
DC 12 V

Publicité

Table des Matières
loading

Table des Matières