3.5.2
DIP switch
The DIP switch on the control circuit board enables regulation and control of setpoints and limit values for
temperatures.
DIP switch (1) position
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
 Switch off the cooling unit for changes to the DIP switch. Ensure that the unit is voltage-free.
The new settings of the DIP switch take effect with next commissioning.
The factory setting is as follows:
 The switch cabinet temperature setpoint is 35°C.
 The maximum switch cabinet temperature is 50°C.
For working on the DIP switch remove the
Operating Manual DTT 6301 Standard Controller (SC) 086100026 © Pfannenberg GmbH
Figure28
Temperatures in °C
Switch position 4 OFF = °C
3
Setpoint
OFF
25°C
OFF
30°C
OFF
35°C
OFF
35°C
ON
40°C
ON
40°C
ON
45°C
ON
45°C
unit cover .Unit cover removal, see
-
DIP switch
Switch position 4 ON = °F
Max. limit value
Setpoint
45°C
77°F
45°C
86°F
45°C
95°F
50°C
95°F
50°C
104°F
55°C
104°F
55°C
113°F
60°C
113°F
front panel removal.
Temperatures in °F
Max. limit value
113°F
113°F
113°F
122°F
122°F
131°F
131°F
140°F
Page 26 / 42