7. ERROR INDICATIONS

Im portant note:
When the battery is completely discharged (battery voltage less than 10V / 20V or 40V), the Quattro will start charging
only w hen AC power is connected to AC-in-1.
For the Quattro to start charging when AC power is connected to AC-in-2, battery voltage must exceed 10V / 20V or
40V.
7.1 General error indications
With the procedures below, most errors can be quickly identified. If an error cannot be resolved, please refer to your Victron
Energy supplier.
Problem
Cause
Quattro will not switch ov er
Circuit breaker or f use in the
to generator or mains
AC-in input is open as a result of ov erload.
operation.
Inv erter operation not
The battery v oltage is excessiv ely high or too low.
initiated when switched on.
No v oltage on DC connection.
"Low battery " LED f lashes.
The battery v oltage is low.
"Low battery " LED lights.
The conv erter switches of f because the battery
v oltage is too low.
"Ov erload" LED f lashes.
The conv erter load is higher than the nominal load.
"Ov erload" LED lights.
The conv erter is switched of f due to excessiv ely
high load.
"Temperature" LED f lashes
The env ironmental temperature is high, or the load
or lights.
is too high.
"Low battery " and "ov erload"
Low battery v oltage and excessiv ely high load.
LEDs f lash intermittently .
"Low battery " and "ov erload"
Ripple v oltage on the DC connection exceeds
LEDs f lash simultaneously .
1,5Vrms.
"Low battery " and
The inv erter is switched of f due to an excessiv ely
"ov erload" LEDs light.
high ripple v oltage on the input.
One alarm LED lights and
The inv erter is switched of f due to alarm activ ation
the second f lashes.
by the lighted LED. The f lashing LED indicates that
the inv erter was about to switch of f due to the
related alarm.
The charger does not operate. The AC input v oltage or f requency is not within the
range set.
Circuit breaker or f use in the
AC-in input is open as a result of ov erload.
The battery f use has blown.
The distortion or the AC input v oltage is too large
(generally generator supply ).
The charger does not operate.
MultiPlus is in "Bulk protection" mode thus, the maximum
"Bulk" LED flashes and "Mains
bulk charging time of 10 hours is exceeded.
on" LED illuminates.
Such
(e.g. a battery cell short-circuit).
The battery is not completely
Charging current excessiv ely high, causing premature
charged.
absorption phase.
Poor battery connection.
The absorption v oltage has been set to an incorrect
lev el (too low).
The f loat v oltage has been set to an incorrect lev el
(too low).
The av ailable charging time is too short to f ully charge
the battery .
The absorption time is too short. For adaptiv e
charging this can be caused by an extremely high
charging current with respect to battery capacity , so
that bulk time is insuf f icient.
The battery is ov ercharged.
The absorption v oltage is set to an incorrect lev el
(too high).
The f loat v oltage is set to an incorrect lev el (too
high).
Poor battery condition.
a
long charging time could indicate a system error
Solution
Remov e ov erload or short circuit on AC-out-1 or AC-
out-2, and reset f use/breaker.
Ensure that the battery v oltage is within the correct
range.
Charge the battery or check the battery connections.
Charge the battery or check the battery connections.
Reduce the load.
Reduce the load.
Install the conv erter in cool and well-v entilated
env ironment, or reduce the load.
Charge the batteries, disconnect or reduce the load,
or install higher capacity batteries. Fit shorter and/or
thicker battery cables.
Check the battery cables and battery connections.
Check whether battery capacity is sufficiently high,
and increase this if necessary .
Install batteries with a larger capacity . Fit shorter
and/or thicker battery cables, and reset the inv erter
(switch of f , and then on again).
Check this table f or appropriate measures in regard
to this alarm state.
Ensure that the AC input is between 185 VAC and 265
VAC, and that the f requency is within the range set
(def ault setting 45-65Hz).
Remov e ov erload or short circuit on AC-out-1 or AC-
out-2, and reset f use/breaker.
Replace the battery f use.
Turn the settings WeakAC and dy namic current limiter
on.
Check your batteries.
NOTE: You can reset the error mode by switching off and
back on the MultiPlus.
The standard MultiPlus factory setting of the "Bulk
protection" mode is switched on. The "Bulk protection"
mode can be switched off with help of VEConfigure only.
Set the charging current to a lev el between 0.1 and 0.2
times the battery capacity .
Check the battery connections.
Set the absorption v oltage to the correct lev el.
Set the f loat v oltage to the correct lev el.
Select a longer charging time or higher charging
current.
Reduce the charging current or select the 'f ixed'
charging characteristics.
Set the absorption v oltage to the correct lev el.
Set the f loat v oltage to the correct lev el.
Replace the battery .
23