Installation
Warning: After removing the unit from the shipping container, check for damage or missing parts. (Refer to the parts list below.)
If you notice a problem, visit www.tripplite.com/support for service. Do not attempt to operate a damaged unit.
Accessory Parts List:
Exhaust Duct
Cooling Duct
(Longer Tube)
(Shorter Tube)
Unit Placement
1
Place the unit on a flat, level surface near a grounded AC outlet rated in accordance with the
unit nameplate (90-110% of specified voltage). Leave adequate space around the unit for
ventilation, with rear and vented sides not less than 20 inches (51 cm) from walls or other
obstacles. Place the unit in a location with convenient access to a drop ceiling or window to
provide the straightest, shortest path available for the flexible exhaust duct. If you plan to use
the flexible cooling duct to focus cool air on a specific rack enclosure or device, place the unit
near the targeted rack enclosure or device to provide the straightest, shortest path available for
the cooling duct.
Warning: Do not use an extension cord to connect the unit to an AC outlet. Use only the
power cord that came with the unit.
Note: If the unit will operate in a confined space (such as closet), you must supply makeup air
in order to maintain airflow efficiency. A 100 in.
bottom of the door should supply adequate makeup air for a typical closet. Consult applicable
building codes for more information.
Cooling Duct Connection (Optional)
2
The pre-installed louvered vent insert is appropriate for room cooling applications. If you plan
to cool a room, skip step 2 and proceed to step 3. If you plan to use the flexible cooling duct to
focus cool air on a specific device or rack enclosure, follow the instructions below.
2-1
Remove the louvered vent insert
2-2
Align the cooling duct adapter
into place.
Book 1.indb 4
Exhaust Duct
Adjustable
Adapter
Exhaust Panel
(2 Sections)
2
(645 cm
2
) or larger vent installed near the
A
by pulling it outward and upward.
A
in the vent opening and push it downward until it snaps
Nut
Bolt
Cooling Duct
Adapter
1
2-1
2-2
4
Louvered Vent
Drainage
Insert
Plug
(Pre-Installed)
100 in.
2
(645 cm
2
) Vent
(For Confined Spaces)
> 20 in (51 cm)
> 20 in (51 cm)
A
A
7/29/2011 9:34:29 AM