Physical Specifications - MarelliMotori MEC-100 Manuel De L'utilisateur

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Loss of sensing
Diode Monitoring
2.10. CONTACTS
Input contacts
Output relays
2.11. ENVIRONMENT
Operating temperature
Storage temperature

2.12. PHYSICAL SPECIFICATIONS

Weight
Dimensions
2.13. TYPE TEST
2.13.1. EMC
Emissions
Emission: Reference standard EN 61000-6-3 (2001) + EN 61000-6-3/A11 (2004)
Test specifications
EN 55022
EN 55022
EN 55014-1
EN 61000-3-2
EN 61000-3-3
963857137_M
Alarm time delay
Excitation current ripple
levels and time delays
Type
Function
Function
Rated data
Max switched voltage
Max switched current
Max switched power
Range
Range
Total weight
Length
Width
Height
Environmental Phenomena
Conducted disturbance
Radiated disturbance
Discontinuous disturbance voltage
Harmonic current emissions
Voltage fluctuations and flicker
<1s
1 low failure level
Range from 0 to 100% of the rated excitation current
1% increment
Time delay from 0 to 100s
1s increment
1 high failure level
Range from 0 to 100% of the rated excitation current
1% increment
Time delay from 0 to 10s
1s increment
Dry contacts, only for devices equipped with galvanically
insulated outputs
START (excitation start contact)
STOP (excitation stop contact)
UP (increase setpoint)
DOWN (decrease setpoint)
PAR (enable par. operation with gen.)
PF/VAR (enable VAR/PF regulation)
VMATCH (enable voltage matching)
FCR (enable FCR mode)
Relays individually associated to alarm functions
1A @ 120Vac / 24Vdc resistive
AC: 120V
DC: 60V
1A
120VA, 30W
Da -30 a +70°C
Da -40 a +80°C
2000g
353.0mm
183.5mm
52.5mm
MEC-100 – Marelli Motori
Result
Complies
Complies
Complies
Complies
Complies
60

Publicité

Table des Matières
loading

Table des Matières