Troubleshooting - Watts Big Bubba Manuel D'installation, D'utilisation Et D'entretien

Une solution complète de système pour toute la maison pour la réduction du plomb, des pfoa/pfos (substances perfluoroalkylées), des kystes, et du goût et de l'odeur de chlore
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Troubleshooting

TROUBLESHOOTING
ISSUE
Contaminant(s) present in
outlet water
Volumetric flow monitor is
not tracking water usage
Alarm does not clear when
flow monitor is reset
Water leak at inlet/outlet
plumbing adaptor
Water leak at filter housing lid
Water leaks from pressure
Damaged O-ring or foreign debris in pressure relief assembly Clean pressure relief valve and replace if required
relief button
Low pressure at outlet
White or milky colored water
from system
!
WARNING
*Change Batteries ONLY when screen is dormant and
NO water is flowing through the flow meter. If water is
flowing and screen is on when batteries are changed,
the last usage volume will not be saved.
16
IOM-WQ-BB-S100
POSSIBLE CAUSE
Filter cartridge has exceeded its capacity
O-ring damage on filter cartridge
Filter cartridge is broken or defective
Bypass valve is open
System is too small for the application
Batteries need to be replaced
Foreign debris in flow meter
Flow monitor cable is not properly connected to meter
Flow meter is installed backwards
Bypass valve is open
Defective flow monitor
Battery power is low
O-ring is damaged or not seated properly
Union nuts are loose
O-ring is damaged or not seated properly
Eye bolt nuts are loose
Filter cartridge clogged with sediment
System is too small for the application
Air in filter system
2130
CORRECTIVE ACTION
Replace filter cartridge and reset flow monitor
Replace filter cartridge and reset flow monitor
Replace filter cartridge and reset flow monitor
Close bypass valve
Ensure water flow does not exceed systems rated GPM
Replace batteries, replace filter cartridge and reset flow monitor*
Clean meter of foreign debris, replace filter cartridge and reset flow monitor
Check cable connection, replace filter cartridge and reset flow monitor
Install flow meter with arrow pointing in the direction of flow, replace filter cartridge
and reset flow monitor
Close bypass valve
Replace flow monitor and replace filter cartridge
Replace batteries*
Replace plumbing adaptor O-ring
Fully hand tighten union nuts
Replace filter housing lid O-ring
Fully hand tighten eyebolt nuts in an opposing pattern
Install a 5 micron pre-sediment filter before system, replace filter cartridge and reset
flow monitor
Ensure water flow does not exceed system's rated GPM
Fully purge air from system using pressure relief button and run water through system
until water runs clear
EDP# 68110146
© 2021 Watts

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Bb-s100

Table des Matières