Electrical Connection - EUCHNER N01 Mode D'emploi

Masquer les pouces Voir aussi pour N01:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Operating Instructions
Precision Single Limit Switches N01/NB01/SN01
Correct use
Precision single limit switches series N01/NB01/
SN01 are interlocking devices without guard locking
(with safety function). The actuator is uncoded (e.g.
dog). In combination with a movable safety guard
and the machine control, this safety component pre-
vents dangerous machine functions from occurring
while the safety guard is open. A stop command is
triggered if the safety guard is opened during the
dangerous machine function.
For general applications, snap-action switching
elements that are not positively driven are used. For
usage as safety switches, only the switching element
ES588 with positively driven NC contacts is allowed.
This means:
Starting commands that cause a dangerous ma-
f
chine function must become active only when the
safety guard is closed.
Opening the safety guard triggers a stop com-
f
mand.
Closing a safety guard must not cause automatic
f
starting of a dangerous machine function. A
separate start command must be issued. For
exceptions, refer to EN  ISO  12100 or relevant
C-standards.
Devices from this series can be used as safe position
encoders.
Before the device is used, a risk assessment must
be performed on the machine, e.g. in accordance
with the following standards:
EN ISO 13849-1, Safety of machinery – Safety-re-
f
lated parts of control systems – Part 1: General
principles for design
EN  ISO  12100, Safety of machinery – General
f
principles for design – Risk assessment and risk
reduction
IEC  62061, Safety of machinery – Functional
f
safety of safety-related electrical, electronic and
programmable electronic control systems
Correct use includes observing the relevant require-
ments for installation and operation, particularly
based on the following standards:
EN ISO 13849-1, Safety of machinery – Safety-re-
f
lated parts of control systems – Part 1: General
principles for design
EN ISO 14119 (supersedes EN 1088), Safety of
f
machinery – Interlocking devices associated with
guards – Principles for design and selection
EN  60204-1, Safety of machinery – Electrical
f
equipment of machines.
Important!
The user is responsible for the proper integration
f
of the device into a safe overall system. For this
purpose, the overall system must be validated,
e.g. in accordance with EN ISO 13849-2.
If the simplified method according to section 6.3
f
of EN ISO 13849-1:2008 is used for determining
the Performance Level (PL), the PL might be re-
duced if several devices are connected in series.
Logical series connection of safe contacts is
f
possible up to PL  d in certain circumstances.
More information about this is available in
ISO TR 24119.
If a product data sheet is included with the prod-
f
uct, the information on the data sheet applies
in case of discrepancies with the operating
instructions.
Safety precautions
WARNING
Danger to life due to improper installation or due
to bypassing (tampering). Safety components
perform a personal protection function.
Safety components must not be bypassed,
f
turned away, removed or otherwise rendered
ineffective. On this topic pay attention in partic-
ular to the measures for reducing the possibility
of bypassing according to EN ISO 14119:2013,
section 7.
Mounting, electrical connection and setup only
f
by authorized personnel possessing special
knowledge about handling safety components.
Function
Precision single limit switches are used for posi-
tioning and control applications in mechanical and
systems engineering.
The switching elements are actuated by means of
plungers. Different plunger types and trip dogs are
used depending on the application (operating point
accuracy and approach speed) (see Figure 2).
In general applications the plunger is actuated by
trip dogs in accordance with DIN 69639 which
are mounted with an interference fit in trip rails in
accordance with DIN 69638.
The switching contacts are actuated when the actu-
ating element is moved from the free position to the
end position. The safety contacts
opened in this process.
Switching states
The detailed switching states for your switch can be
found in Figure 11. All available switching elements
are described there.
Actuating element in free position
The safety contacts
are closed.
Actuating element in end position
The safety contacts
are open.
Mounting
NOTICE
Device damage due to improper mounting and
unsuitable ambient conditions.
Safety switches and actuators must not be used
f
as an end stop.
Observe EN ISO 14119:2013, sections 5.2 and
f
5.3, for information about fastening the safety
switch and the actuator.
Observe EN  ISO  14119:2013, section 7, for
f
information about reducing the possibilities for
bypassing an interlocking device.
It is imperative that dimension 11
f
from switch reference surface to trip dog, see
Figure 3) is maintained in safety circuits to ensure
safe contact opening.
Protect the switch head against damage.
f
Protection against environmental
influences
Safety venting valves (see Figure 3, for example)
are used to compensate for the pumping action of
the plungers. They must not be sealed with paint.
Mask plunger, plunger guide, safety venting valves
f
and rating plate during painting work!
Changing the actuating direction
90°
Figure 1: Changing the actuating direction
4
1. Unscrew the locking screw.
2. Set the required direction.
3. Screw in the locking screw again.

Electrical connection

WARNING
Loss of the safety function due to incorrect
connection.
Use only safe contacts (
f
Use of the safety switch as an interlocking
device for personnel protection
At least one contact
the position of the safety guard (for terminal assign-
ment, see Figure 11).
The following information applies to devices
with plug connector:
Check that the plug connector is sealed.
f
The following information applies to devices
with cable entry:
1. Use a suitable tool to open the desired inser-
tion opening.
2. Fit the cable gland with the appropriate degree
of protection.
3. Connect and tighten the terminals (for terminal
assignment, see Figure 11; for tightening
torque values, see technical data).
4. Check that the cable entry is sealed.
5. Close the switch cover and screw in place
are positively
(tightening torque 1.2 Nm).
Function test
WARNING
Fatal injury due to faults during the function test.
Before carrying out the function test, make sure
f
that there are no persons in the danger area.
Observe the valid accident prevention regula-
f
tions.
Check the device for correct function after installa-
tion and after every fault.
Proceed as follows:
Mechanical function test
The actuating element must move easily. Close the
safety guard several times to check the function.
Electrical function test
1. Switch on operating voltage.
2. Close all safety guards.
The machine must not start automatically.
¨
¨
3. Start the machine function.
4. Open the safety guard.
The machine must switch off and it must not be
¨
¨
possible to start it as long as the safety guard
(distance
is open.
-0,5
Repeat steps 2 - 4 for each safety guard.
Inspection and service
WARNING
Danger of severe injuries due to the loss of the
safety function.
In safety circuits, the entire switch must be re-
f
placed in case of damage or wear. Replacement
of individual parts or assemblies is not permitted.
Check the device for proper function at regular
f
intervals and after every fault. For informa-
tion about possible time intervals, refer to
EN ISO 14119:2013, section 8.2.
Inspection of the following is necessary to ensure
trouble-free long-term operation:
correct switching function
f
secure mounting of all components
f
precise adjustment of trip dog in relation to single
f
limit switch
damage, heavy contamination, dirt and wear
f
) for safety functions.
must be used. This signals

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Nb01Sn01

Table des Matières