LEGRAND Daker DK 4.5 kVA Manuel D'installation page 45

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
COnsTrUCTiOn
sPeCifiCATiOns
Weights
Dimensions L x H x P in mm
Protection
Ambient specifications
Operating temperature range
Operating relative humidity range
Degree of protection as per IEC529
Noise level at 1 meter
electrical input specifications
Rated input voltage
Range of input voltage
Rated input frequency
Maximum input current
Number of input phases
Waveform on output
With battery operation
Type of operation
electrical specifications on output
Rated output voltage
Active output capacity
on nominal load
Apparent output capacity on
nominal load
Overload capacity
Number of phases on output
Daker DK 4.5, 6, 10 kVA
3 100 56
3 100 57
25 Kg
25 Kg
440 x 88 x 680 440 x 88 x 680
Electronic protection against overloading
and short-circuiting. Shutdown on reaching operating
limit and overheating.
Automatic shutdown due to protection triggering
from 20 to 80% non-condensing
230 V
from 160 V to 280V
50 or 60 Hz ± 5Hz
25 Arms
33 Arms
on line - double conversion
4.05kW
5.4 kW
4.5kVA
6 KWA
105% continuous
120% for 30 seconds
140% for 10 seconds
Single phase
3 100 58
26 Kg
440 x 132 x 680
from 0 to +40 °C
IP21
< 50 dBA
54,3 Arms
Single phase
sinusoidal
230 V ± 2%
9 kW
10 KWA
3 100 59
380 V
from 227V
to 485V
Three phase
45

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Daker dk 6 kvaDaker dk 10 kva

Table des Matières