Perry Electric 1TPTE530 Mode D'emploi page 35

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

PROGRAMMABLE FUNCTIONS TO ADAPT TO THE TYPE OF INSTALLATION
DURATION OF THE PROPORTIONAL CYCLE
The duration of the control cycle for the
from to
7
20
minutes; a long cycle is advisable for systems with
high thermal inertia (cast iron radiators, floor heating systems)
and a short cycle for systems with low thermal inertia (fan coil).
The default setting is
10
minutes.
ADJUST OR EXCLUDE ANTIFREEZE PROTECTION
When the thermostat is
PROP
mode can be set
system in case of frost when the temperature goes below +4.0
°C (+39.2 °F); thus setting is adjustable from +4.0 °C to +12.0
°C (+39.2 °F ÷ +53.6 °F).
It is possible to exclude this function.
In this case the system will be exposed to eventual damage
caused by frost.
Press the
or
key
to set the duration of
The proportional control
cycle.
Press the
OK
key to save
and pass on to the
subsequent setting or keep
pressed for at least 4
seconds to save the new
setting and exit program
menu.
, it is programmed to protect the
OFF
Press the
or
s e t t h e r e q u i r e d
antifreeze temperature
reading.
Press the
OK
key to save
and return to the °C/°F
scale setting or keep
pressed for at least 4
seconds to save the new
setting and exit program
menu.
If instead the exclusion
o f t h e a n t i f r e e z e
protection os required,
press the
key until
the display shows
a n d c o n f i r m b y
p r e s s i n g
O K
explained above.
EN
key to
- - - -
, a s
35

Publicité

Table des Matières
loading

Table des Matières