To ensure that the performance of your chiller is not impaired, we recommend that you only use original spare parts purchased
from Pfannenberg, in this way you ensure the reliability and quality of the machine.
If you have any questions about spare parts, please contact our Pfannenberg Service Team (Contact details, p.2).
If you need any consultancy in terms of a maintenance and leakage check according (EU) No. 517/2014 please contact our
Pfannenberg Service Team. To ensure the proper and reliable functionality of the chiller, we recommend to perform the
commissioning by our Pfannenberg Service Team.

3. Residual risks

There are some residual risks after the installation of the unit that have to be considered:
Residual risks according to 2006/42/CE Directive:
The condenser has fins on his external surface, so there is the possibility for the operator to touch sharp edges during
service of the unit.
Although the unit is designed with all the possible safety requirements, in case of external fire there is the possibility that the
internal pressure and temperature of the unit will increase in a dangerous and uncontrollable way; in that case use the
extinguishing tools suitable for that conditions.
For units without emergency switch-disconnector: chiller user must install the emergency switch-disconnector installation
close to the chiller, in an accessible and clearly visible place, to allow emergency stop of the unit and safety for the
operator.
Even if the instructions contained in this manual are enough explanatory for safety, high pressure switches are mounted, to
guarantee intervention in case of wrong filing, or in case of malfunction due to not controlled increase of pressure and
temperature.
Residual risks according to 2014/68/UE Directive:
Although the unit is designed with all the possible safety requirements, in case of external fire there is the possibility that the
internal pressure and temperature of the unit will increase in a dangerous and uncontrollable way; in that case use the
extinguishing tools suitable for that conditions.
For the series production of the standard units of category , the pressure resistance test (typically the hydrostatic pressure
test) is made on a statistic base, not on all units.
This can be accepted, also considering all the safety devices mounted on the units.
For units without emergency switch-disconnector: chiller user must install the emergency switch-disconnector installation
close to the chiller, in an accessible and clearly visible place, to allow emergency stop of the unit and safety for the
operator.
Even if the instructions contained in this manual are enough explanatory for safety, high pressure switches/safety valves
are mounted, to guarantee intervention in case of wrong filing, or in case of malfunction due to not controlled increase of
pressure and temperature.

4. Receiving and Unpacking

Each chiller is supplied on a wooden pallet, wrapped with protective film, strapped, and protected on lateral sides. Each unit is
contained in a carton box.
It is recommended to pay particular attention during handling and transportation of the unit and to maintain the packaged units
in the vertical position, in order to avoid any kind of dents to the external frame and any damage to the internal components.
Secure units to the transport vehicle with suitable strapping.
Note!
The above mentioned packages are suitable for piling up units on top of each other (max 2 units)
Store the Chiller in a dry place, away from heat sources. All waste materials should be recycled in the appropriate manner.
For the operations of lifting and movement it is necessary to use a fork lift truck with proper load capacity and with forks longer
than the base of the Chiller. Avoid sudden movements which can damage the framework and the internal components.
PFANNENBERG Std Chiller (above 45Kg weight) can be provided with 4 eyebolts for lifting and transportation; to be used for
vertical loading/unloading only (to see the right point for lifting please refer to the stickers on the unit). Where eyebolts are not
installed as standard, they can be provided as accessory.
Caution:
the chiller must be transported and moved without liquid/s in the tank/s
70040-122_01-_-(PC2500_Op._Manual_IT-EN-DE-FR-ES-RU).docx
English
6