Check the electrical alarm systems and controls.
Check the filling of the tank (visual level). If the system is filled with a glycol-mix, refill only with the same mix.
Check that pressure, flow rate and temperature values of the hydraulic circuit are included into the limits indicated on the
machine label.
If the chiller is equipped with an air filter, the filter has to be changed/cleaned monthly, or, if required in a shorter time
interval
The condenser must be cleaned in monthly intervals, or, if required in shorter time intervals. To have access to the right
side of the condenser, open the cover of the chiller, and remove the bracket on the lateral side of the condenser, cleaning it
from the interspace between the condenser and the fan. Only compressed air (not water or solvents) must be used to clean
the surface of the condenser. The fins of the condenser must not have any dust deposits or residual products or sludges on
their surface.
70040-122_01-_-(PC2500_Op._Manual_IT-EN-DE-FR-ES-RU).docx
English
Picture 17 – Fan placement
Picture 18/19 – Air filter changing
Picture 20/21 – Condenser cleaning