WALL MOUNTING (boiler)
Condensate connection
• Screw the evacuation nozzle into the product at the release level
• A water trap having H=50 mm min. must imperatively be used
• Connect the evacuation nozzle to the 32 diameter water trap with a sufficient and regular slope
• Before starting up fill the water trap with water
• Place the condensate evacuation in a frost free zone if necessary
Boiler mounting
The motor, heat exchanger and bypass (option) are
supplied pre-assembled. A mounting kit comprising
2 wall-mounting angles is supplied.
• Drill into the wall as per the diagrams below
• Insert adequate wall plugs
• Fix the 2 wall-mounting angles with screws
• Hook the equipment onto the mounting angles.
• For the collection of condensates, install the
condensate evacuation nozzle as shown opposite, to
the exchanger release