Technical Informations / Functioning / Parameters; Menu Items / Adjustable Parameters - IFM efector500 PP70 Série Notice Utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6 Technical information / Functioning / Parameters

Menu items / Adjustable parameters

(when connected to programming unit)
Switch-on point 1 / 2
Upper limit value at which the output changes its switching status.
• setting range: 1 ... 100% of the value of the
measuring range
• indicated in the set unit (bar, PSI, MPa or kPa)
Switch-off point 1 / 2
Lower limit value at which the output changes its switching status.
• setting range: 0.5 ... 99.5% of the value of the
measuring range
• indicated in the set unit (bar, PSI, MPa or kPa)
rPx is always lower than SPx. The unit does not accept values for
rPx which are higher than SPx.
Changing the switch-on point also changes the switch-off point
(the distance between SPx and rPx remains constant).
If the distance is higher than the new switch point, it is automati-
cally reduced (rPx is set to the minimum setting value).
Configuration of pin 4 (output 1 / communication interface)
5 settings can be selected:
- Hno = hysteresis / normally open
- Hnc = hysteresis / normally closed
- Fno = window function / normally open
- Fnc = window function / normally closed
- EPS = The sensor transfers its data to the programming and
Configuration of pin 2 (output 2 / Teach input)
5 settings can be selected:
- Hno = hysteresis / normally open
- Hnc = hysteresis / normally closed
- Fno = window function / normally open
- Fnc = window function / normally closed
- tch = pin 2 is the input for the Teach signal; the settings for
For the functioning of the connector pins 2 and 4 → page 31
28
display unit via pin 4; the settings for SP1 and rP1 are
not effective.
SP2 and rP2 are not effective.