Please note the following during the installation:
- Archive this operating instructions so that they are available at any time.
- Install Heating unit in a dry, frost-free and draught-free room.
- Automatic vent valve has to be installed at the highest point of the circuit in this room. If highest
point is not situated in a frost-free room, the valve has to be insulated or maintained frost-free
with a heating cable.
- Heating Unit has to be mounted horizontally.
- Never use heating unit without water. This can follow to the damage of the heating unit and of
the pump.
- Circulation pump must run on position 3.
- Circuit pipes must be insulated, minimum thickness 30 mm, heat conductivity
- Do not use plastic pipes, which are suited only for cold water.
- Adjusted temperature refers to the return water flow temperature.
- Electrical installation must be completely done by an authorized electrician.
- Max. length of insulated circuit (return flow inclusive) should not exceed 250 m (820 feet).
- All electric cables and pipes have to be protected against possible mechanical damages or
possible damages by animals.
- Attention! In case of deaeration hot water can escape.
- During maintenance or repair, the unit has to be separated from main current.
Important:
If water comes from your own source, take care that water reserve is enough, otherwise you
risk a pressure drop. This happens, when e.g. animals drink a lot of water at the same time.
This pressure drop leads to the creation of a vacuum in the water line.
To equalize this vacuum, air streams through the valves operated by the animals directly
into the water circuit.
These air bubbles can lead to the trigging of the STB in the heating element.
In case of a domestic (own) water supply, a water store tank / pressure intensifier
has to be installed.
1

Installation Instructions

Bleeding of circulation pump
Attention! When bleeding the hot water can escape!
2
0,04 /
W
mK
3
23