Summer Position
Action
Switch in - 0 - position
Winter Position
Switch in - 1 - position
Adjust return flow temperature
Fractory adjustment +10° C
Heating
Control-lamp at the heating element only
illuminates if the heating element is heating.
Temperature at STB sensor
(Security Temperature Limiter)
exceeds 90° C
Errors / Interferences
Heating element does not heat,
water is not getting warm.
Pump is not running
20
Control System
Reaction: Heating Unit
Circulation pump and heating element are off.
Control lamp at heating element is off.
Circulation pump runs.
Heating element is ready for operation.
-> Heating unit starts to heat, when the return water flow
temperature falls below the adjusted temperature.
Heating unit warms up the water until the adjusted water
temperature value is reached at the thermostat (a
desired temperature of return water flow is adjusted at the
thermostat, mounted on the return flow pipe).
Control lamp at heating element illuminates.
After having reached the desired temperature, heating
element switches off --> Control lamp at heating element
stops to illuminate. If return flow water temperature is lower
than the adjusted value, the heating element will be
automatically switched on again...
Control lamp at heating element switches off. Security
temperature limiter (STB) triggers. Heating element stops to
heat. After cooling down phase -> it is necessary to switch
on STB manually!
See description for STB activation, page 24 .
- Main switch stands on - 0 - position
- Plug of heating element is not connected
- Residual current device (RCD) is activated
- STB of the heating element is activated
- Flow temperature did not yet fall below the adjusted
temperature (at thermostat of the return water flow pipe)
- Water circulation is interrupted
- Heating element is out of order
- Too long water circuit (max. 250 meter / 820
- Leakage in circuit
- Too big water consumption
- Too many drinking bowls are connected
- Insulation is out of order / damaged
- Check the N
on-return flap and its
- Boil protection thermostat has trigged. Once the the flow
temperature reaches the fixed value of 40° C the heating
element turns off.
- Main switch in - 0 - position
- RCD protection switch is activated
- Water circulation is interrupted
- Pump is damaged
- Air is in the pump
feet of pipes
water flow direction.
)