LIGHTS CODE

Green
Green
Yellow
Yellow
Red
OFF
The charging station is energized.
The charging station is energized. The total
load exceeds 80%. If the loads exceed 80% for
a predetermined period, the charging station
will be de-energized.
The charging station is not energized. The total
loads exceed 80%. The resumption time will
start when the total load is lower than 80%.
The charging station is not energized. The total
load is lower than 80% and the recovery time is
in progress. Each flash mean two (2) minutes
before the resumption of power to the charging
station. (ex: 3 flashes = 6 minutes before power
to the charging station). During that period, if
the total load exceeds 80%, the recovery time
will restart from the beginning.
Malfunction:
1. Check all connections and voltage.
2. Check the DIP switch configuration settings.
3. Check if the current transformers (CT) are
properly connected and interlocked.
4. Check if the connection for the current
transformers are properly connected to the
PCB electronics.
5. If the problem persists, send pictures of the
installation at support@dccelectric.com
and then call 1 (833) 717-1355.
No power. Check the power source.