3.4 Calibration

• Go to
  Current 
• Short-circuit connections 3 and 4 on
the converter.
• Calibrate the instrument if a current
is indicated of more than + or - 0.2 A.
• Press both push buttons simultane-
ously for at least 3 seconds to cali-
brate the instrument, see '5 Calibra-
tion current measurement'.
• Remove the short-circuit and re-con-
nect the converter to the shunt.

3.5 Charge condition

Make sure that the battery is fully
charged
• Go to
  Charge 
• Press both push buttons simultane-
ously for at least 3 seconds to set 100
% charge condition, see '6 Setting
100 % charge condition' .
16
090433.01
, see '2 Operation'.
, see '2 Operation'.

3.6 Setting alarms

3 different alarms can be set using the
instrument:
- battery charge condition too low:
standard setting 20.0%
- battery voltage too low:
standard setting 10.0 V
- battery voltage too high:
standard setting 30.0 V
• Follow the directions given in '1 Sum-
mary Operation and Setup' to set the
alarms.