5. Connect the batteries to the BATTERY INPUT. (Step4)
WIRING FAULT LED will illuminate and make an audible alarm to indicate the wiring polarity is reversed.
6. If the battery box or the battery connection has a switch, please turn it on first.
7. Turn on the BATTERY SW. on the back of the machine (Step 5)
8. Turn on the Power Switch and switch the Output Selector to Normal on the
front panel. The Power On Indicator and the LCD Module Display will blink
4 times. Press the Display toggle (Selected Switch) once. The
output voltage showing on the LCD Module Display should be
220V. This completes the start-up process. (Step 6)
9. Press and hold the Display toggle switch for 4 seconds then release.
The machine will begin a self test and enter Battery Mode for 6
seconds before returning to Line Mode. Make sure the self test is
ready, or see the Definitions for illuminated LCD on page 10 for a list
of alarm code definitions.
10. After ensuring the machine works normally, reassemble the back
cover. The installation is now complete.
11. When the external battery needs to be maintained or replaced remember to turn the machine off.
Once off, remove the AC power source and switch off the BATTERY SW. before maintenance or
replacing the batteries. When the work is complete, please start from Step 1 to re-install the machine.
7
Step 4
Copyright © 2011 CyberPower Systems, Inc.
CPS7500PRO/CPS7500PIE
Step 5
Step 6